Soft Starter Internal Register Address - Danfoss VLT Compact Starter MCD 201 Installation Manual

Ethernet/ip module
Hide thumbs Also See for VLT Compact Starter MCD 201:
Table of Contents

Advertisement

Packet Structures
Byte
Bit
45
0–7
Table 7.2 Structures Used for Querying the Status of the Soft Starter
1) For models MCD5-0053B and smaller, this value is 10 times greater than the value shown on the LCP.
2) Product type code: 4=MCD 200, 5=MCD 500.
3) Reading bytes 14–15 (changed parameter value) reset byte 12 (changed parameter number) and bit 0 of byte 17 (parameters have changed).
Always read bytes 12 and 17 before reading bytes 14–15.
4) Bits 2–7 of byte 17 report the soft starter's trip or warning code. If the value of bits 0–4 of byte 16 is 6, the soft starter has tripped. If bit 5=1, a
warning has activated and the soft starter continues operation.
5) Powerscale functions as follows:
0 = Multiply power by 10 to get W.
1 = Multiply power by 100 to get W.
2 = Power is shown in kW.
3 = Multiply power by 10 to get kW.

7.4 Soft Starter Internal Register Address

7
7
Internal registers within the soft starter have the functions listed in Table 7.3. These registers are not directly accessible via
fieldbus.
Register
Description
0
Version
1
Device details
2
2)
Changed parameter number
Changed parameter value
3
2)
4
Soft starter state
5
Current
6
Current
16
EtherNet/IP Module
Function
Reserved
Bits
0–5
6–8
9–15
0–7
8–15
0–13
14–15
0–4
5
6
7
8
9
10–15
0–13
14–15
0–9
10–15
Danfoss A/S © 05/2017 All rights reserved.
Details
Details
Binary protocol version number.
Product parameter list version.
1)
Product type code.
0 = No parameters have changed.
1~255 = Index number of the last parameter changed.
Total number of parameters available in the soft starter.
Value of the last parameter that was changed, as indicated in register 2.
Reserved.
0 = Reserved.
1 = Ready.
2 = Starting.
3 = Running.
4 = Stopping.
5 = Not ready (restart delay, restart temperature check).
6 = Tripped.
7 = Programming mode.
8 = Jog forward.
9 = Jog reverse.
1 = Warning.
0 = Warning.
1 = Initialized.
0 = Local control.
1 = Remote control.
0 = Parameters have changed.
1 = No parameters have changed.
0 = Negative phase sequence.
1 = Positive phase sequence.
3)
See trip codes in Table 7.4.
Average rms current across all 3 phases.
Reserved.
Current (% motor FLC).
Reserved.
2)
4)
MG17M202

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT Compact Starter MCD 201 and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Vlt compact starter mcd 202Vlt soft starter mcd 500

Table of Contents