Packet Structures
7.3 Status Commands (Read Only)
NOTICE
Some soft starters do not support all functions.
Byte
Bit
0
1
2
3
0
4
5
6
7
7
7
1
0–7
2–3
0–15
0–7
1)
4
0–7
5
1)
6
0–7
7
0–7
0–5
6–8
8–9
9–15
10
0–7
11
0–7
3)
0–7
12
13
0–7
0–13
14–15
14–15
14
EtherNet/IP Module
Function
Trip
Warning
Running
Reserved
Ready
Control from net
Local/Remote
At reference
Status
Trip/warning code
Motor current (low byte)
Motor current (high byte)
Motor 1 temperature
Motor 2 temperature
Reserved
Product parameter list version
2)
Product type code
Reserved
Reserved
Changed parameter number
Parameters
3)
Changed parameter value
Reserved
Danfoss A/S © 05/2017 All rights reserved.
Details
1 = Tripped.
1 = Warning.
0 = Unknown, not ready, ready to start, or tripped.
1 = Starting, running, stopping, or jogging.
–
0 = Start or stop command not acceptable.
1 = Start or stop command acceptable.
1 = Always, except in program mode.
0 = Local control.
1 = Remote control.
1 = Running (full voltage at the motor).
0 = Unknown (menu open).
2 = Soft starter not ready (restart delay or thermal delay).
3 = Ready to start (including warning state).
4 = Starting or running.
5 = Soft stopping.
7 = Trip.
8 = Jog forward.
9 = Jog reverse.
See trip codes in Table 7.4.
Current (A).
Motor 1 thermal model (%).
Motor 2 thermal model (%).
–
–
–
–
–
0 = No parameters have changed.
1~255 = Index number of the last parameter changed.
Total numbers of parameters available in the soft starter.
Value of the last parameter that was changed, as indicated in byte 12.
–