Danfoss VLT Compact Starter MCD 201 Installation Manual page 19

Ethernet/ip module
Hide thumbs Also See for VLT Compact Starter MCD 201:
Table of Contents

Advertisement

Packet Structures
Register
Description
7
Motor temperature
8
5)
Power
9
% Power factor
10
Reserved
4)
Current
11
4)
Current
12
Current
13
4)
14
Reserved
15
Reserved
16
Reserved
17
Parameter list version number
18
Digital input state
19–31
Reserved
Table 7.3 Functions of Internal Registers
1) Product type code: 4=MCD 200, 5=MCD 500.
2) Reading register 3 (changed parameter value) resets registers 2 (changed parameter number) and 4 (parameters have changed). Always read
registers 2 and 4 before reading register 3.
3) Bits 10–15 of register 4 report the soft starter's trip or warning code. If the value of bits 0–4 is 6, the soft starter has tripped. If bit 5=1, a
warning has activated and the soft starter continues operation.
4) For models MCD5-0053B and smaller, this value is 10 times greater than the value shown on the LCP.
5) Powerscale functions as follows:
0 = Multiply power by 10 to get W.
1 = Multiply power by 100 to get W.
2 = Power is shown in kW.
3 = Multiply power by 10 to get kW.
MG17M202
Installation Guide
Bits
Details
0–7
Motor 1 thermal model (%).
8–15
Motor 2 thermal model (%).
0–11
Power.
12–13
Power scale.
14–15
Reserved.
0–7
100% = power factor of 1.
8–15
Reserved.
0–15
0–13
Phase 1 current (rms).
14–15
Reserved.
0–13
Phase 2 current (rms).
14–15
Reserved.
0–13
Phase 3 current (rms).
14–15
Reserved.
0–7
Parameter list minor revision.
8–15
Parameter list major revision.
For all inputs, 0 = open, 1 = closed (shorted).
0 = Start.
0–15
1 = Stop.
2 = Reset.
3 = Input A.
4–15
Reserved.