Download Print this page

Technical Data; Measured Values - E+E Elektronik EE150 User Manual

Humidity and temperature transmitter for hvac applications

Advertisement

tECHniCAL dAtA

(Modification rights reserved)

Measured values

Relative Humidity
Working range
Accuracy at 20°C
Temperature dependency
Temperature
Working range
T-Accuracy at 20°C
Outputs
Analog output
(0...100% RH; T: see ordering guide)
Passive T-sensor
2-wire
Wires resistance (terminal - sensor)
General
Power supply (Class III)
for 0 - 10 V
for 4 - 20 mA
Current consumption
Connection
Housing material
Protection class
Cable gland
Sensor protection
Electromagnetic compatibility
Working conditions
Storage conditions
SEtUP And AdJUStmEnt
The EE150 is ready to use and does not require any configuration by the user. The factory setup of EE150 corresponds to the type num-
ber ordered. For ordering guide please see data sheet at www.epluse.com/EE150.
If needed, the user can change the factory setup by using the optional
Product Configuration Software (EE-PCS). With these
humidity and temperature.
For product data sheet EE-PCA please see www.epluse.com.
The E+E Product Configuration Software (EE-PCS) is free and can be downloaded from www.epluse.com/configurator.
USA
FCC notice:
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate ra-
dio frequency energy and, if not installed and used in accordance with the installation manual, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or
more of the following measures:
-
Reorient or relocate the receiving antenna.
-
Increase the separation between the equipment and receiver.
-
Connect the equipment into an outlet on a circuit different from that to which thereceiver is connected.
-
Consult the dealer or an experienced radio/TV technician for help.
CANADIAN
ICES-003 Issue 5:
CAN ICES-3 B / NMB-3 B
InformatIon
Langwiesen 7 • A-4209 Engerwitzdorf
Tel: +43 7235 605-0 • Fax: +43 7235 605-8
info@epluse.com • www.epluse.com
LG Linz Fn 165761 t • UID-Nr. ATU44043101
Place of Jurisdiction: A-4020 Linz • DVR0962759
10...90% RH
±3% RH (30...70%RH), otherwise ±5% RH
typ. ±0.05% RH/°C
-5...55°C
(23...131°F)
±0.3°C
0-10 V
R
≥ 10k Ohm
L
4-20 mA (2-wire)
R
≤ 500 Ohm
L
see ordering guide
typ. 0.5 Ohm
15 - 35V DC or 24V AC ±20%
10V + R
x 20 mA < U
< 35V DC
L
V
with DC power supply typ. 5mA
with AC power supply typ. 13mA
Screw terminals, max. 1.5 mm
Polycarbonate, UL94V-0 approved
IP65/NEMA 4
M16 x 1.5
PTFE filter, non-removable
EN61326-1 EN61326-2-3 Industrial environment
FCC Part 15 Class B ICES-003 Issue 5 Class B
-5...55°C
(23...131°F)
-25...60°C
(-13...140°F)
E+E Product
one can set the output scaling, and perform one or two point adjustment for
+43 7235 605 0 / info@epluse.com
eff
2
0...95% RH (non-condensing)
20...80% RH
Configuration Adapter (EE-PCA) and the E+E
BA_EE150_e // v1.0 // Technische Änderungen vorbehalten

Advertisement