user's guiDe
ee10 - hVac room transmitter for relative humidity and temperature with
digital rs485 interface
GENERAL
EE10 combines relative humidity (RH) and temperature (T) measurement in one device with modern design. The RH and T mea-
sured data is available either on a BACnet or Modbus RTU interface. Additionally, it calculates the dewpoint temperature (Td),
absolute humidity (dv), mixing ratio (r), enthalpy (h), frost point temperature (Tf) and water vapor partial pressure (e).
CAutioN
The device shall not be exposed to extreme mechanical or thermal stress.
This device is not appropriate for safety, emergency stop or other critical applications where device malfunction or failure could
cause injury to human beings.
The electronics board is an ESD sensitive device, please handle it accordingly and avoid touching it during installation.
Please allow min. 5 minutes warm up time for the device to reach the specified measurement performance.
DiMENSioNS / MouNtiNG
The electronic of EE10 is located in the front cover, which can be easily snapped on/off once the back cover is fixed onto the wall
(D = mounting holes) and wired.
eu version
85 / 3.35"
79.7 / 3.14"
4 / 0.16"
38.2 / 1.5"
Opening the enclOsure
Press to release the latch A till the enclosure can be opened. Use a
screwdriver or a pen.
clOsing the enclOsure
Set the front cover into flute B, rotate it like C and press it onto the
back cover till the latch A snaps in.
impOrtant
In order to protect the front cover and the electronics from typical
construction site pollution (such as painting of the walls) the front
cover should be snapped on only after the construction works are
completed.
As EE10 is generally mounted onto a conduit box, for accurate
measurement results it is important to tighten the conduit box for
avoiding false air ingress (along the electrical tubes inside the wall)
into the EE10 enclosure.
us version
85 / 3.35"
79.7 / 3.14"
60 / 2.36"
38.2 / 1.5"
8 / 0.31"

Advertisement

loading

Summary of Contents for E+E Elektronik EE10

  • Page 1 Please allow min. 5 minutes warm up time for the device to reach the specified measurement performance. DiMENSioNS / MouNtiNG The electronic of EE10 is located in the front cover, which can be easily snapped on/off once the back cover is fixed onto the wall (D = mounting holes) and wired.
  • Page 2 The serial number as ASCII-code is located at register address 30001-30008. The firmware version is located at register address 30009. The measured values are saved as a 32Bit float value from 0x19 to 0x2F. The required units (metric or non-metric) must be selected in the „Ordering guide“, see EE10 data sheet. FLoAt (read register): iNFo (read register): Register Communication...
  • Page 3 The EE10 transmitter is ready to use and does not require any configuration by the user. The factory setup of EE10 corresponds to the type number ordered. For ordering guide please see data sheet at www.epluse.com/ee10. If need, the user can change the factory setup by using the optional Configuration Adapter Cable HA011066 and the E+E Product Configuration Software (EE-PCS).
  • Page 4 Test report according to DIN EN10204 - 2.2 • Quick Guide - EE10 with digital interface. fcc notice: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.