Figure 2-9 Read Input Status Example - Data Field - Siemens SIMATIC TI505 User Manual

Modnim
Hide thumbs Also See for SIMATIC TI505:
Table of Contents

Advertisement

SIMATIC TI505/TI500 MODNIM User Manual
The response returns in the data field a single byte (1A) containing the 1's
or 0's for the 5 discrete inputs, packed out with zeros for the three high bits.
1A =
0 0 0 1 1 0 1 0
Figure 2-9 Read Input Status Example — Data Field
Input 0A (OFF)
Input 0B (ON)
Input 0C (OFF)
Input 0D (ON)
Input 0E (ON)
Packed with zeros (000)
Modbus Commands
2-11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic ti500

Table of Contents