1.7

Establishing Communications

Verifying that the
MODNIM is Logged
into the PLC
SIMATIC TI505/TI500 MODNIM User Manual
After installing and configuring the MODNIM, you should verify that the
module is properly logged into the PLC I/O map.
NOTE: The PLC I/O map is the first thing to check if the PC GOOD
(PC/NIM COMM GOOD) indicator light is off.
Connect your programming device to the PLC to verify PLC-to-MODNIM
module communication by following these steps.
1.
Access the Configure I/O function menu, then execute Show.
2.
Execute the Read Base function.
3.
Check all the I/O points on the base that the MODNIM is installed in.
Once you have entered the appropriate commands, the programming
device displays a chart listing all slots on the base and the inputs and
outputs associated with each slot. If a row on the chart is blank, then
the corresponding base slot does not contain a module. Figure 1-14
shows a sample I/O definition chart with a MODNIM installed in Slot 1
of a four-slot base. (Refer to your TISOFT manual for detailed
instructions.)
I/O Address
The module is logged in
as eight outputs (Ys).
I/O MODULE DEFINITION FOR :
I/O
Slot
Address
1
.....
0001
2
.....
0000
3
.....
0000
4
.....
0000
Slot Number
Install the module into any
available I/O slot in the I/O base.

Figure 1-14 Sample I/O Definition Chart

Base Number
Displays number
of the current base.
CHANNEL 1 BASE 00
Number of Bit and Word I/O
X
Y
WX
.....
00
..
08
..
00
.....
00
..
00
..
00
.....
00
..
00
..
00
.....
00
..
00
..
00
Special
WY
Function
..
00
.......
..
00
.......
..
00
.......
..
00
.......
SF Module
The MODNIM is logged in as
a Special Function Module.
Installation and Set-up
Yes
No
No
No
1-19