Setting the Dipswitches (continued)
Side V iew of Module,
Faceplate Up
Dipswitches
Dipswitch Settings
Push Down
Left
C COILS
RTS/CTS: OFF
ASCII MODE
PARITY: EVEN
PARITY: ON
STOPBITS: 1
0
0
0
0
0
1-8
Installation and Set-up
NIM GOOD —
Base power and
MODNIM operating status
XMT —
Data Transmit indicator
ON LINE —
Connected to the Modbus network.
Continuous ON indicates remote mode;
flashing indicates local mode
Network
Configuration
Network
Address
Push Down
Right
10
Y OUTPUT
9
RTS/CTS: ON
8
RTU MODE
7
PARITY: ODD
6
PARITY: OFF
5
STOPBITS: 2
4
1
DATA
3
1
RATE
2
1
SELECT
1
1
8
1
7
2
6
4
Network
5
8
4
16
Address
3
32
2
64
1
128

Figure 1-5 Series 505 MODNIM Switches and LEDs

Series 505 MODNIM
Data Transmission
Rate Settings
Switches
1 2 3 4
Baud
0 0 0 0 –
50
0 0 0 1 –
50
0 0 1 0 –
75
0 0 1 1 –
110
0 1 0 0 –
150
0 1 0 1 –
200
0 1 1 0 –
300
0 1 1 1 –
600
1 0 0 0 –
1200
1 0 0 1 –
1800
1 0 1 0 –
2400
1 0 1 1 –
3600
1 1 0 0 –
4800
1 1 0 1 –
7200
1 1 1 0 –
9600
1 1 1 1 – 19200
SIMATIC TI505/TI500 MODNIM User Manual
MODNIM
PC GOOD —
PLC/MODNIM
NIM
PC
communication
GOOD
GOOD
link status
REC —
XMT
REC
Receiving Data
indicator
ON
LINE
TEST
TEST —
Test mode status
REMOTE
LOCAL
TEST
RESET
PORT A
PORT B
505-5184