C.1
Environmental Specifications
C-2
Specifications
The Series 505 I/O subsystem is tested against some of the most stringent
standards in the world. Table C-1 lists specifications that are common to
Series 505 I/O devices.

Table C-1 Environmental Specifications

Operating Temperature
Storage Temperature
Relative Humidity
Pollution Degree
Vibration
Sinusoidal
Random
Impact Shock
Electric Noise Immunity
Conducted noise:
Radiated noise:
Electrostatic discharge:
System Isolation
Torque for bezel screws
Corrosion Protection
Agency Approvals
0 to 60 C (32 to 140 F)
–40 to +70 C (–40 to 158 F)
5% to 95% non-condensing
2, IEC 664, 664A
IEC 68-2-6, Test Fc;
0.15 mm, peak-to-peak, 10–57 Hz;
1.0 g 57–150 Hz
NAVMAT P-9492 or IEC 68-2-34
2
Test Fdc with 0.04 g
/Hz, 80–350 Hz, and
3 dB/octave rolloff, 80–20 Hz and
350–2000 Hz at 10 min/axis
IEC, 68-2-27, Test Ea; Half sine, 15 g 11 ms
IEC 801, Part 4, Level 3
MIL STD 461B, Part 4; CS01, CS02, CS06
IEC 255-4
EEC 4517/79 Com(78) 766 Final, Part 4
IEEE 472, 2.5 kV
IEC 801, Part 3, Level 3
MIL STD 461B, Part 4; RS01, RS02
IEC 801, Part 2, Level 4, (15 kV)
Isolation (user-side to controller-side): 1500 Vrms
0.3 N-m (2.61 in.-lbs.) minimum
0.6 N-m (5.22 in.-lbs.) maximum
All parts are of corrosion resistant material or are
plated or painted as corrosion protection.
ULr Listed (UL508 industrial control equipment)
CSAr Certified (CSA142 process control equipment)
FM Approved (Class I, Div. 2, Hazardous locations)