28
RHDE250 to RHDE4000 (Contrac) ELECTRICAL ROTARY ACTUATOR | OI/RHDE250_4000-EN REV. B
... 7 Electrical connections
Connection of cable shielding
Sensor-connection chamber
1
2
4
5
1 Cover for connection chamber
2 Cover groove
3 Screw
4 Cable clip
Figure 13: Connection of the cable shielding in the sensor connection chamber
Change from two to one column
4
3
4
7
6
5 Cable sheath
6 Housing
7 Shielding
1. Insert screw.
2. .Unscrew the cover for the connection chamber
3. Cut the cable sheath to the required length.
4. Separate the cable shield and pull it back over the outer
sheath
5. Push the cable through the cable gland and fasten it with the
cable clip
6. Make sure that the cable shield is in contact with the clip and
the housing.
7. Connect cable in accordance with Electrical connections on
6
page 26.
8. Check the cable connections for tight fit and fasten the cable
gland.
9. Screw the cover of the connection chamber back on tight.
10. Loosen the screw to the point where until it is pressing
against the cover
inserted in a groove in the cover
5
Note
When installing the cover for the connection area, take care not
M11060
to damage the sealing ring. If the sealing ring is damaged,
contact the manufacturer.
Motor connection chamber
Apply the cable shield to the motor in a suited manner.
. Make sure that the screw is fully
1
.
b