Specifications
Ambient temperature
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Derating for high altitude, see special conditions in the Design Guide
EMC standards, Emission
EMC standards, Immunity
See section on special conditions in the Design Guide.
≤ 3.7 kW (200-240 V), ≤ 7.5 kW (400-480 V)
1)
Only for
2)
As enclosure kit for
3)
Derating for high ambient temperature, see special conditions in the Design Guide

8.5 Cable Specifications

Cable lengths and cross-sections for control cables
Max. motor cable length, screened
8
8
Max. motor cable length, unscreened
Maximum cross section to control terminals, flexible/ rigid wire without cable end sleeves
Maximum cross section to control terminals, flexible wire with cable end sleeves
Maximum cross section to control terminals, flexible wire with cable end sleeves with collar
Minimum cross section to control terminals
1)
For power cables, see electrical data tables in 8.1 Electrical Data.

8.6 Control Input/Output and Control Data

Digital inputs
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
Maximum voltage on input
Pulse frequency range
(Duty cycle) Min. pulse width
Input resistance, R
Safe Torque Off Terminal 37
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Maximum voltage on input
Typical input current at 24 V
Typical input current at 20 V
Input capacitance
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1)
Terminals 27 and 29 can also be programmed as output.
52
VLT
3)
≤ 3.7 kW (200-240 V), ≤ 7.5 kW (400-480 V)
2)
2)
i
3, 4)
(Terminal 37 is fixed PNP logic)
®
HVAC Drive Operating Instructions
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
1)
MG11AJ02 - Rev. 2013-07-31
Max. 50 °C (24-hour average maximum 45 °C)
EN 61800-3, EN 61000-6-3/4, EN 55011
EN 61800-3, EN 61000-6-1/2,
1.5 mm
0.5 mm
0.25 mm
18, 19, 27
0 °C
- 10 °C
-25 to +65/70 °C
1000 m
150 m
300 m
2
/16 AWG
1 mm
2
/18 AWG
2
/20 AWG
2
/24AWG
4 (6)
1)
1)
1)
, 29
, 32, 33,
PNP or NPN
0-24 V DC
<5 V DC
>10 V DC
>19 V DC
<14 V DC
28 V DC
0-110 kHz
4.5 ms
approx. 4 kΩ
0-24 V DC
<4 V DC
>20 V DC
28 V DC
50 mA rms
60 mA rms
400 nF