Danfoss VLT FC 102 Operating Instructions Manual page 32

1.1-90 kw hvac drive
Hide thumbs Also See for VLT FC 102:
Table of Contents

Advertisement

Application Set-up Examples
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
6
6
A IN
54
COM
55
A OUT
42
COM
39
Table 6.6 Pulse Start/Stop
Speed
Latched Start (18)
Stop Inverse (27)
Illustration 6.3 Latched Start/Stop Inverse
30
®
VLT
HVAC Drive Operating Instructions
Parameters
Function
Setting
5-10 Terminal 18
[9] Latched
Digital Input
Start
5-12 Terminal 27
[6] Stop
Digital Input
Inverse
* = Default Value
Notes/comments:
If 5-12 Terminal 27 Digital Input
is set to [0] No operation, a
jumper wire to terminal 27 is
not needed.
D IN 37 is an option.
MG11AJ02 - Rev. 2013-07-31
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 6.7 Start/Stop with Reversing and 4 Preset Speeds
6.1.3 External Alarm Reset
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 6.8 External Alarm Reset
Parameters
Function
Setting
5-10 Terminal 18
[8] Start
Digital Input
5-11 Terminal 19
[10]
Digital Input
Reversing*
5-12 Terminal 27
[0] No
Digital Input
operation
5-14 Terminal 32
[16] Preset
Digital Input
ref bit 0
5-15 Terminal 33
[17] Preset
Digital Input
ref bit 1
3-10 Preset
Reference
Preset ref. 0
25%
Preset ref. 1
50%
Preset ref. 2
75%
Preset ref. 3
100%
* = Default Value
Notes/comments:
D IN 37 is an option.
Parameters
Function
Setting
5-11 Terminal 19
[1] Reset
Digital Input
* = Default Value
Notes/comments:
D IN 37 is an option.