Specifications
380-480 V
Enclosure
Power [kW]
type
A2
1.1-4.0
A3
5.5-7.5
B3
11-18
B4
22-37
C3
45-55
C4
75-90
A4
1.1-4
A5
1.1-7.5
B1
11-18.5
B2
22-30
C1
37-55
C2
75-90
Table 8.12 380-480 V, Enclosure Types A, B and C
525-600 V
Enclosure
Power [kW]
type
A3
5.5-7.5
B3
11-18
B4
22-37
C3
45-55
C4
75-90
A5
1.1-7.5
B1
11-18
B2
22-30
C1
37-55
C2
75-90
Table 8.13 525-600 V, Enclosure Types A, B and C
®
VLT
HVAC Drive Operating Instructions
Recommended
Recommended
fuse size
Max. fuse size
gG-10 (1.1-3)
gG-16 (4)
gG-16
gG-40
gG-50 (22)
gG-63 (30)
gG-80 (37)
gG-100 (45)
gG-150 (45)
gG-160 (55)
gG-160 (55)
aR-200 (75)
aR-250 (90)
gG-10 (1.1-3)
gG-16 (4)
gG-10 (1.1-3)
gG-16 (4-7.5)
gG-40
gG-50 (22)
gG-63 (30)
gG-80 (37)
gG-100 (45)
gG-160 (55)
aR-200 (75)
aR-250 (90)
Recommended
Recommended
fuse size
Max. fuse size
gG-10 (5.5)
gG-16 (7.5)
gG-25 (11)
gG-32 (15-18)
gG-40 (22)
gG-50 (30)
gG-63 (37)
gG-63 (45)
gG-100 (55)
aR-160 (75)
aR-200 (90)
gG-10 (1.1-5.5)
gG-16 (7.5)
gG-25 (11)
gG-32 (15)
gG-40 (18.5)
gG-50 (22)
gG-63 (30)
gG-63 (37)
gG-160 (37-45)
gG-100 (45)
aR-250 (55)
aR-160 (55)
aR-200 (75-90)
MG11AJ02 - Rev. 2013-07-31
Recommended circuit
breaker (Moeller)
gG-25
PKZM0-25
gG-32
PKZM0-25
gG-63
PKZM4-50
gG-125
NZMB1-A100
NZMB2-A200
aR-250
NZMB2-A250
gG-32
PKZM0-25
gG-32
PKZM0-25
gG-80
PKZM4-63
gG-100
NZMB1-A100
gG-160
NZMB2-A200
aR-250
NZMB2-A250
Recommended circuit
breaker (Moeller)
gG-32
PKZM0-25
gG-63
PKZM4-50
gG-125
NZMB1-A100
gG-150
NZMB2-A200
aR-250
NZMB2-A250
gG-32
PKZM0-25
gG-80
PKZM4-63
gG-100
NZMB1-A100
NZMB2-A200
aR-250
NZMB2-A250
Max. trip level [A]
25
25
50
100
150
250
25
25
63
100
8
160
250
Max. trip level [A]
25
50
100
150
250
25
63
100
160
250
57