Electronic Models - Electronic models have a
fi xed rate gas valve. Input of electronic models
is shown in Table 3.
Electronic Models with Fixed Rate Gas Valve
Natural and Propane Gas
Model Series
Input Rate (BTU / HR)
SSBV-3530CNE
SSBV-4035CNE
Table 3
BTU Input - Electronic Models
Gas Pressure - All Models
Tables 4, 5 & 6 show the units' gas pressure
requirements:
Inlet Gas Supply Pressure (all models)
Fuel #
Minimum
5.0" WC
Natural Gas
(1.24 kPa)
11.0" WC
Propane
f i r e - p a r t s . c o m
(2.74 kPa)
Table 4
Manifold Gas Supply Pressure
(millivolt models)
Fuel #
Low
Natural
(Lo) 2.2" WC
Gas
(.55 kPa)
(Lo) 6.3" WC
Propane
(1.57 kPa)
Table 5
Manifold Gas Supply Pressure
(electronic models)
Fuel #
Max. Manifold Pressure
Natural Gas
(Hi) 3.5" WC (.87 kPa)
Propane
(Hi) 10.0" WC (2.49 kPa)
Table 6
Test gauge connections are provided on the
front of the millivolt gas control valve, identi-
fi ed IN for the inlet and OUT for the manifold
side. A 1/8" NPT Test gauge connection
is provided at the inlet and outlet side of
the electronic gas control valve.
These appliances must be isolated from the gas
supply piping system (by closing their individual
manual shut-off valve) during any pressure test-
ing of gas supply piping system at test pressures
equal to or less than 1/2 psig (3.5 kPa).
These appliances and their individual shut-off
valves must be disconnected from the gas
supply piping system during any pressure
testing of that system at pressures greater
than 1/2 psig (3.5 kPa).
Orifi ce Sizes - Sea Level to High Altitude
(All Models)
These appliances are tested and approved for
installation at elevations of 0-4500 feet (0-1372
meters) above sea level using the standard burner
orifice sizes (marked with an "*" in Table 7). For
elevations above 4500 feet, contact your gas
supplier or qualifi ed service technician. Install
the appliance according to the regulations of
23,000
the local authorities having jurisdiction and, in
29,000
the USA, the National Fuel Gas Code NFPA 54
/ ANSI Z223.1 - latest edition or, in Canada, the
CAN1-B149.1 and .2 codes - latest edition.
Elevation 0-4500 feet ( 0-1372 meters)
Model
Series
Maximum
SSBV-3530
10.5" WC
(2.61 kPa)
SSBV-4035
13.0" WC
* Standard size installed at factory
(3.23 kPa)
• Part /Cat. Number
Table 7

MASSACHUSETTS REQUIREMENTS

High
These appliances are approved for installation in
the following USA locations listed below:
(Hi) 3.5" WC
(.87 kPa)
Installation of these fi replaces are approved
for installation in the US state of Massachu-
(Hi) 10.0" WC
setts if the following additional requirements
(2.49 kPa)
are met -
• Installation and repair must be done by a
plumber or gas fi tter licensed in the Com-
monwealth of Massachusetts.
• The fl exible gas line connector used shall not
exceed 36 inches (92 centimeters) in length.
• The individual manual shut-off must be a
T-handle type valve.
Gas Valve Diagrams
See Figures 1 & 2 for Millivolt models and
Figure 3 For Electronic Models.
HI/LO Variable
Flame Height
Adjustment
Pilot Adjustment
Screw
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Burner Orifi ce Sizes
Natural
Propane
Gas
Gas
drill size (inches)
drill size (inches)
2.3 mm (.090")
*
#54 (.055")
37L70 •
99K79 •
#36 (.1065")
*
#52 (.0635")
18L4001 •
LB-55874D •
SIT Millivolt Gas Valve
Inlet Pressure Tap
Manifold Pressure Tap
Main Gas
Control Knob
Figure 1
OFF/PILOT/ON
Honeywell Millivolt Gas Valve
PILOT
ADJUSTMENT
GAS CONTROL
SCREW
KNOB
TP/TH
TP
TH
WIRING
INLET
TERM-
PRESSURE
INALS
TAP
Figure 2
Honeywell Electronic Gas Valve
Manifold Pressure
Port
*
*
Figure 3
SAFETY WARNIINGS
If the information in this
manual is not followed
exactly, a fi re or explosion
may result causing prop-
erty damage, personal
injury or loss of life.
WARNING
This appliance is only for use
with the type of gas indicated on
the rating plate. This appliance
is not convertible for use with
other gases, unless a certifi ed
kit is used.
AVERTISSEMENT
Cet appareil doit être utilisé
uniquement avec les types de
gaz indiqués sur la plaque sig-
nalétique. Ne pas l'utiliser avec
d'autres gaz sauf si un kit de con-
version certifi é est installé.
PIEZO
IGNITER
CONVERTIBLE
HI/LO REGULATOR
(adjusts fl ame height
and heat output)
OUTLET
PRESSURE
TAP
ON / OFF Switch
Inlet
Pressure
Port
Electronic Gas
Control Valve
WARNING
3