Superior SDVPF-N-B Installation Instructions Manual

Sdvst direct-vent gas fireplaces
Hide thumbs Also See for SDVPF-N-B:

Advertisement

P/N 700037M Rev. F 01/2011
This manual is one of a set of two supporting this product.
Refer to P/N 725035M for Care and Operation Instructions.
Ce manuel est disponible en francais, simplement
en faire la demande. Numéro de la pièce 700037CF.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
INSTALLATEUR : Laissez cette notice avec l'appareil.
CONSOMMATEUR : Conservez cette notice pour
consultation ultérieure.
This appliance may be installed as an OEM installation in a manufactured home (USA only) and must be
installed in accordance with the manufacturer's instructions and the Manufactured Home Construction and
Safety Standard, Title 24 CFR, Part 3280, in the United States or the Standard for Installation in Manufactured
Homes, CAN/CSA Z240 MH, in Canada. This appliance is only for use with the type of gas indicated on the
rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
WARNING / AVERTISSEMENT / AVISO
• HOT GLASS WILL CAUSE
BURNS.
• DO NOT TOUCH GLASS
UNTIL COOLED.
• NEVER ALLOW CHILDREN
TO TOUCH GLASS.
WARNING: If the information in these instructions
is not followed exactly, a fire or explosion may
result, causing property damage, personal injury,
or death.
-
vapors and liquids in the vicinity of this or any other
appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
instructions.
department.
- Installation and service must be performed by a
INSTALLATION INSTRUC TIONS
SDVST Direct-Vent
Gas Fireplaces
MODELS
OTL Report No. 116-F-32-5
• UNE SURFACE VITRÉE CHAUDE
PEUT CAUSER DES BRÛLURES.
• LAISSER REFROIDIR LA SURFACE
VITRÉE AVANT D'Y TOUCHER.
• NE PERMETTEZ JAMAIS À UN ENFANT
DE TOUCHER LA SURFACE VITRÉE.
AVERTISSEMENT : Assurez-vous de bien suivre les
instructions données dans cette notice pour réduire au
minimum le risque d'incindie ou d'explosion ou pour
éviter tout dommage matériel, toute blessure ou la mort.
- Ne pas entreposer ni utilizer d'essence ni d'autres vapeurs
ou liquides inflammables dans le voisinage de cet appareil
ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
• Ne pas tenter d'allumer d'appareil.
• Ne touchez à aucan interrupteur. Ne pas vous servir des
téléphones se trouvant dans le bâtiment où vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis
un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service des incindies.
- L'installation et l'entretien doivent être assurés par un
installateur ou un service d'entretien qualifié ou par le
fournisseur de gaz.
MILLIVOLT:
SDVST-N-B
SDVPF-N-B
Portland
US
• EL VIDRIO CALIENTE
CAUSARÁ QUEMADURAS.
• USTED DEBE NUNCA
TOCAR EL VIDRIO CALIENTE.
• LOS NIÑOS DEBEN NUNCA
TOCAR EL VIDRIO.

Advertisement

Table of Contents
loading

Summary of Contents for Superior SDVPF-N-B

  • Page 1 INSTALLATION INSTRUC TIONS SDVST Direct-Vent Gas Fireplaces P/N 700037M Rev. F 01/2011 This manual is one of a set of two supporting this product. Refer to P/N 725035M for Care and Operation Instructions. MODELS MILLIVOLT: Ce manuel est disponible en francais, simplement en faire la demande.
  • Page 2: Table Of Contents

    TABLE OF CONTENTS PACKAGING GENERAL INFORMATION Packaging .........Page 2 The assembled vented gas fireplace heater is WARNING Introduction ........Page 2 packaged with: General Information ......Page 2 Young children should be care- 1 - One log set located in firebox area. Requirements for the fully supervised when they are 2 - One envelope containing the literature pack-...
  • Page 3 Note: Installation and repair should be done The appliance, when installed, must be electri- WARNING cally grounded and wired in accordance with by a qualified service person. The appliance local codes or, in the absence of local codes, should be inspected before use and at least Improper installation, adjust- with the National Electrical Code, ANSI/NFPA annually by a professional service person.
  • Page 4: Requirements For The Commonwealth Of Massachusetts

    Gas Pressure - All Models Orifice Sizes - Sea Level to High Altitude Gas Valve Diagrams - See Figure 1. (All Models) Tables 2 and 3 show the appliances' gas These appliances are tested and approved for pressure requirements: HI/LO Variable Inlet Pressure Tap installation at elevations of 0-4500 feet (0-1372 Flame Height...
  • Page 5: Cold Climate Insulation

    COLD CLIMATE INSULATION For cold climate installations, seal all cracks around your appliance with noncombustible material and wherever cold air could enter Vertical Horizontal Vent the room. It is especially important to insulate Vent (top vent) outside chase cavity between studs and under floor on which appliance rests, if floor is above ground level.
  • Page 6: Vent Termination Clearances

    VENT TERMINATION CLEARANCES Vertical Vent Termination Clearances Termination Heights For Vents These instructions should be used as a Above Flat Or Sloped Roofs TERMINATION HEIGHTS FOR VENTS ABOVE guideline and do not supersede local codes FLAT OR SLOPED ROOFS Ref. NFPA 54 / ANSI Z223.1 Horizontal Overhang in any way.
  • Page 7 VENT TERMINATION CLEARANCES EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS NOTE: Local Codes Or Regulations May Require Different Clearances. See Item D in the Text Below. NOTE: Location Of The Vent Termination Inside Exterior Wall Must Not Interfere With Access To The Corner Detail Electrical Service.
  • Page 8: Appliance And Vent Clearances

    Appliance and Vent Clearances MINIMUM CLEARANCES TO COMBUSTIBLES Maintain clearances from appliance to Hearth Extension - A hearth extension is not required with this appliance. If a hearth extension is used, do not block the lower control compartment access door. Any hearth extension used is for appearance combustible materials as detailed in Table only and does not have to conform to standard hearth extension installation requirements.
  • Page 9: Detailed Installation Steps

    TYPICAL INSTALLATION SEQUENCE Step 1. FRAMING WARNING The typical sequence of installation is outlined Frame these appliances as illustrated in Figures Failure to position the parts in below. However, each installation is unique 11 or 12. All framing details must allow for a accordance with these diagrams and may result in variations to the steps minimum clearance to combustible framing...
  • Page 10: Fireplace And Framing Specifications

    FIREPLACE SPECIFICATIONS - MODEL SDVST (SEE-THROUGH) • Inches (millimeters) Fireplace Framing SPECIFICATIONS • Minimum Framing Stud Size is 2 x 4 Specifications • See side views of fireplace below for Natural & Propane 37,500 gas line inlet location options. (MV Low 30,000) Gas BTU Input **25-1/4 11-3/8...
  • Page 11 FIREPLACE SPECIFICATIONS - MODEL SDVPF (PENINSULA VIEW) Fireplace Framing Specifications • Inches (millimeters) SPECIFICATIONS • Minimum Framing Stud Size is 2 x 4 • See right side viewsof fireplace below for gas line inlet location options. Natural & Propane 37,500 inches (millimeters) **25-1/4 11-3/8...
  • Page 12: Step 2. Routing Gas Line

    Notes: Step 2. ROUTING GAS LINE Proper Sizing of Gas Line • All appliances are factory-equipped with a flexible gas line connector and 1/2 inch shutoff Properly size and route the gas supply line Route a gas line along the inside of the right side valve (see Figure 47 on Page 28).
  • Page 13: Step 3. Install The Vent System

    Step 3. INSTALL THE VENT SYSTEM Vent Seal Cap Insulation General Information These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CSA-B149.1 in Canada.
  • Page 14: Vertical Termination Systems

    VERTICAL TERMINATION SYSTEMS (ROOF) VENT SECTION LENGTH CHART VENT SECTION LENGTH CHART See Figure 17 and Figures 28 to 32 (Pages 18 Nominal Nominal Section Length (inches) Section Length and 19) and their associated Vertical Vent Tables i t c (inches) illustrate the vertical venting configurations that Net Section...
  • Page 15 Vertical (Offset) Installation B. Attach vent components to appliance - Se- Push the vent component against the previous cure Vent SV4.5 direct-vent system compo- section until it fully engages, then twist the Analyze the vent routing and determine the nents are unitized concentric pipe components component clockwise running the dimples down number of vent sections and elbows required.
  • Page 16 F. Change vent direction to horizontal / inclined run - At transition from or to a horizontal / in- Outer Pipe Of clined run, install the SV4.5E45 and SV4.5E90 Chimney elbows in the same manner as the straight vent 14" Min. sections.
  • Page 17 Use a carpenter’s level to measure from a I. Install the roof flashing - Extend the vent K. Install the vertical termination - The final constant surface and adjust the support straps sections through the roof structure. Install the Step involves installation of the SV4.5CGV-1 as necessary.
  • Page 18: Vertical Vent Figures And Tables

    VERTICAL VENT FIGURES/TABLES Notes: Table A • Secure Vent™ (rigid vent pipe) is shown V Minimum H Maximum in the Figures; Secure Flex™ (flexible vent Ceiling Firestop / Spacer (SV4.5VF) pipe) may also be used. feet (meter) feet (meter) • It is very important that the horizontal/in- (0.610) (0.305) clined run be maintained in a straight (no...
  • Page 19 VERTICAL VENT FIGURES / TABLES (CONTINUED) Table C Maximum H Maximum V Minimum feet (meter) feet (meter) feet (meter) Ceiling Firestop / (1.524) (0.610) (0.305) Spacer (SV4.5VF) (3.048) (1.219) (0.610) (4.572) (1.829) (0.914) (6.096) (2.438) (1.219) V + V 1 + H + H 1 = 40 feet (12.2 m) Max Wall Firestop/ Spacer (SV4.5HF) H = 8 feet (2.438 meters) Max.
  • Page 20: Horizontal Termination System

    Push the vent component against the previous Support Horizontal / Inclined Run Building section until it fully engages, then twist the Brackets Support component clockwise running the dimples Framing SV4.5HT-2 down and along the incline channels until they Termination SV4.5E90 seat at the end of the channels.
  • Page 21 It is important to maintain the required clear- To help minimize water infiltration it is ances to combustibles: 1" (25 mm) at all sides recommended that the Firestop/Spacer for all vertical runs; and 3" (76 mm) at the (SV4.5HF) be installed on the exterior side of the wall.
  • Page 22: Horizontal Vent Figures And Tables

    See Table 8 as an aid in venting component selection for a particular range of exterior wall thicknesses. Square termination (SV4.5HT-2) shown. H = 28 in. (711 mm) Venting Components Required for Various Exterior Wall Thick- Maximum nesses, when using Square Termination Kit (SV4.5HT-2) 21 in.
  • Page 23 HORIZONTAL VENT FIGURES / TABLES (CONTINUED) Table F V Minimum Maximum H Maximum feet (meter) feet (meter) feet (meter) (1.524) (0.610) (0.305) (3.048) (1.219) (0.610) (4.572) (1.829) (0.914) Wall Firestop/ Spacer (SV4.5HF) (6.096) (2.438) (1.219) V + H + H 1 = 40 feet (12.2 m) Max Ceiling Firestop H = 8 feet (2.438 meters) Max.
  • Page 24 HORIZONTAL VENT FIGURES / TABLES (CONTINUED) When using Secure Flex, use Firestop / Spacer SF4.5VF Wall Firestop / Spacer (SV4.5HF) When using Secure Flex, use Firestop / Spacer SF4.5HF Note: See Table 8 on Page 22 as an aid in venting component selection for a particular range of exterior wall thicknesses.
  • Page 25: Venting Using Flexible Vent Pipe

    VERTICAL OR HORIZONTAL VENTING USING Flex Vent SECuRE FLEX KITS AND COMPONENTS NOTE: Outer pipe is pulled away to show the detail of the inner pipe. Securing Screw - 3 places, Secure Flex™ venting kits and components equally spaced, just below gear clamp.
  • Page 26: Step 4. Field Wiring

    Step 4. FIELD WIRING Note: The gas valve is set in place and pre-wired Receptacle, Junction Box at the factory. and Cover Plate Installation CAUTION Junction Box A. SIT and Honeywell Millivolt Wiring Outlet Receptacle (See Figure 44) Ground supply lead must be con- 1.
  • Page 27: Step 5. Optional Blower Kit Wiring

    See Figure 45. It is not necessary to remove Step 5. WIRING - OPTIONAL FORCED AIR CAUTIONS the outlet box. BLOWER (FBK-100) (See Figure 45) - • Remove the carton support from 3. Connect the ground supply wire to the outlet An optional ON/Off (FRS) control switch is also the control compartment before box green ground screw as shown.
  • Page 28: Step 6. Connecting Gas Line

    Step 6. CONNECTING GAS LINE Gas Flex Line Connector All codes require a shut-off valve mounted in GAS CONNECTION 3/8" NPT x the supply line. The orientation of the shut-off 1/2" x 3/8" Flare Valve Flare Fitting valve should face the front. Figure 47 illustrates Shut-off Valve two methods for connecting the gas supply.
  • Page 29: Step 7. Verifying Appliance Operation

    Note: The (pull-out) Lighting instructions label TEST ALL CONNECTIONS FOR GAS LEAKS Step 8. INSTALLING LOG SET, VOLCANIC can be found in the control compartment (see (FACTORY AND FIELD): STONE AND GLOWING EMBERS Figure 48 on Page 28). WARNING When first lighting the appliance, it will take WARNING a few minutes for the line to purge itself of Never use an open flame to...
  • Page 30 BURNER POSITIONING LOG AND VOLCANIC STONE INSTALLATION Install the unitized log set: NOTE: INSTALL REAR BURNER FIRST, PROCEDURE: THEN FRONT BURNER. a. The bottom of the log set is notched to ac- BURNER BRACKET A commodate the pilot. PORTS REAR BURNER The log set foam package is located in the firebox b.
  • Page 31: Step 9. Installing Glass Doors

    Removing Glass Enclosure Panels Step 10. BURNER ADJUSTMENTS Step 9. INSTALLATION AND REMOVAL (see Figure 55) OF GLASS DOOR Flame Appearance and sooting 1. Remove the top louver assembly by lifting it Proper flame appearance is a flame which is up and pulling it out.
  • Page 32: Step 11. Hood Installation

    Burner Air Shutter Adjustment Procedure Air Shutter Adjusting Burner Air Shutter WARNINGS Venturi Opening Tube ***Main Burner Factory Air Shutter • Air shutter adjustment should Orifice Opening Setting - All Models only be performed by a quali- fied professional service tech- Natural Gas Propane Gas inches (millimeters)
  • Page 33: Step 12. Attaching Safety-In-Operation Warnings

    Step 12. ATTACHING SAFETY-IN-OPERATION WARNINGS It is the installer's responsibility to ensure these warnings are properly affixed during installation. These warning labels are a critical step in informing consumers of safe operation of this appliance. ATTACHING SAFETY-IN-OPERATION APPOSITION DES MISES EN GARDE RELATIVES COLOCACIóN DE ADVERTENCIAS DE WARNINGS à...
  • Page 34: Installation Accessories

    INSTALLATION ACCESSORIES Item Cat. No. Model Description H1968 SV4.5HT-2 Horizontal Square Termination With Firestop / spacer (H2246) & Adapter (74L61) H2152 SV4.5CGV-1 Vertical Termination Cap 77L70 SV4.5L6 6 Inch (152 mm) Vent Section 77L71 SV4.5L12 12 Inch (305 mm) Vent Section 77L72 SV4.5L24 24 Inch (610 mm) Vent Section...
  • Page 35 Item Cat. No. Model Description H1969 SF4.5HT-2 Horizontal Square Termination (without flex) 77L87 SFKIT12S Flex Square Term. (with 12 inch [305 mm] * compressed flex) 77L88 SFKIT18S Flex Square Term. (with 18 inch [457 mm] * compressed flex) 77L89 SFKIT24S Flex Square Term.
  • Page 36 INSTALLATION ACCESSORIES Item Cat. No. Model Description 92L07 SV-MHPK1 Manufactured Home Pipe Kit (SV) - 1/12 Pitch 92L08 SV-MHPK2 Manufactured Home Pipe Kit (SV) - 2/12 Pitch 92L09 SV-FSTFE Firestop Thimble (SV) - Flat, with Extension 92L10 SV-FST1E Firestop Thimble (SV) - 1/12 Pitch, with Extension 92L11 SV-FST2E Firestop Thimble (SV) - 2/12 Pitch, with Extension...
  • Page 37: Gas Conversion Kits

    GAS CONVERSION KITS INSTALLATION INSTRUCTIONS Step 1. TURN OFF THE GAS SUPPLY TO THE WARNING APPLIANCE and disconnect power supply at the circuit breaker. Ensure appliance is cold. This conversion kit shall be installed by a qualified service agency in accor- dance with the manufacturer’s instructions and all applicable codes and CAUTION: THE GAS SUPPLY SHALL BE SHUT OFF PRIOR TO DISCONNECTING THE...
  • Page 38 Step 8. Reassemble the remaining components NOTE: Flame appearance will diminish 4% per SIT Millivolt Gas Valve thousand feet. by reversing the procedures outlined in the preceding steps. NOTE: Each model has two burners and 2 Orifices. Step 9. Attach the conversion label provided Pressure in the conversion kit to the rating plate on the Regulator...
  • Page 39 NOTES...
  • Page 40 Lennox Hearth Products reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information. Printed in U.S.A. © 2006 Lennox Hearth Products 1508 Elm Hill Pike, Suite 108 •...