Celltron ULTRA
Selecting what to measure
The default is VOLT & CONDUCTANCE.
1. Press the ARROW keys to highlight VOLT & CONDUCTANCE, and press ENTER .
2. Press the ARROW keys (or use the numeric keypad) to check the box next to your choice:
VOLTAGE ONLY, VOLT & CONDUCTANCE, VOLTS THEN CONDUCT(ANCE).
NOTE: Select VOLTS THEN CONDUCT(ANCE) if you are measuring conductance and do
not want conductance testing to affect your voltage measurements. After you measure the
voltage of the jars (or jars and straps) in a string, disconnect, then reconnect to the fi rst jar in
the string to complete the test by measuring conductance.
3. Press ENTER to accept.
NOTE: Once you start the conductance portion of the VOLTS THEN CONDUCTANCE test,
you will not be able retest voltage. Be sure to review your voltage reading before you start
your conductance portion of the test.
Selecting the string
The default is 25 °C (77 °F). Conductance measurements vary by jar temperature. To compensate,
the analyzer uses the TEMPERATURE value to adjust the percentage of the reference value you set
in the UTILITIES SETUP as the WARN/FAIL threshold. The percent is compensated to 25 °C (77 °F).
Compensation is adjusted at 0.7% per degree Celsius between 0 °C and 35 °C. (The kit includes an
infrared temperature sensor and instructions.)
1. Press the ARROW keys to highlight TEMPERATURE, and press ENTER .
2. Press the ARROW keys (or use the numeric keypad) to select a value.
3. Press ENTER to accept.
Saving the
BATTERY SETUP
To save your settings for later use, press the ARROW keys to highlight SAVE AND CONTINUE, and
press ENTER . You are returned to the
string, see Selecting the TEST option in Chapter 6: Testing.
To save your settings for immediate testing, connect the clamps or probes and press the ARROW to
highlight SAVE AND TEST. Press ENTER to start the test. (See Chapter 6: Testing.)
(VOLT & CONDUCTANCE)
TEMPERATURE
test menu. To use a saved BATTERY SETUP to test a
NEW
Chapter 5: Selecting test parameters
33
•
•