If the load change, drive voltage rating, motor voltage or DC Bus set-point are different then ∆V is calculated from:
∆V = 80V x K
X K
x K
L
RAT
MV
Where:
K
= load change / 200%
L
K
= Drive voltage rating / 400
RAT
K
= motor voltage / 400
MV
K
= 700 / DC Bus voltage set point
SP
In some applications, particularly with a high d.c. bus voltage set point and low switching frequency it may be necessary to limit the rate of change of
power flow to prevent over voltage trips. A first order filter on the torque reference of the motor drive (i.e. using Pr 4.12) is the most effective method
to reduce the transient further. (A fixed limit of the rate of change of torque demand is less effective.) The following table gives an approximate
indication of the reduction in ∆V for different time constants. (As already mentioned the value of ∆V given if for an instantaneous change of torque
representing the worst case. In applications where a speed controller is used in the motor drive the transient will already include an inherent filter).
Time constant
20mS
40mS
The transient produced is approximately proportional to the voltage controller gain. The default voltage controller gain is set to give a value that is
suitable for most applications. The gain may need to be increased if the DC Bus capacitance is high compared to two drives of similar rating coupled
together. However, care must be taken to ensure that the gain is not too high as this can cause excessive ripple in the DC Bus voltage.

Close start up contactor

3.07
Drive mode
Regen
Bit
SP
Coding
1
Update rate
4ms
When the Regen drive has powered-up through the soft-start and the DC Bus voltage has stopped rising and is higher than the contactor close
voltage this bit changes from 0 to 1. If the DC Bus voltage falls below the contactor open voltage DC or the system is synchronised and the AC
voltage falls below contactor open voltage AC this bit changes to zero. When regen mode is selected this bit is routed to the drive relay output
(Terminals 41/42) as default.
This output, or an alternative output, can be used to control the soft-start contactor.
Drive Rating
Contactor Close
Vac
Vdc
200V
215
400V
430
575V
565
690V
565

Main contactor closed

3.08
Drive mode
Regen
Bit
SP
Coding
1
Default
Regen
Update rate
4ms
When regen mode is selected Pr 3.08 is the destination for the digital input on terminal 25 (T25) as default. This input, or an alternative input, should
be connected to an auxiliary contact on the soft-start contactor so that it follows the state of the contactor. The Regen drive will only attempt to
synchronise to the supply when this parameter is one. This parameter is also used to monitor the contactor when the Regen drive is running. If at any
time this parameter is zero the Regen drive is immediately disabled.

Enable motor drive

3.09
Drive mode
Regen
Bit
SP
Coding
1
Update rate
4ms
When the unit has been enabled and successfully synchronised this bit will become active. If the Regen drive attempts to re-synchronise or trips, this
bit becomes inactive. When regen mode is selected this bit is routed to a the digital output on terminal 24 (T24) as default. The output, or an
alternative output, should be used to enable the motor drive(s) connected to the DC bus of the Regen drive.
Unidrive SP Regen Installation Guide
Issue Number: 2
System
Mechanical
design
installation
X K
SP
Change in ∆V
x 0.75
x 0.5
FI
DE
Txt VM DP
ND
1
Contactor Open
Contactor Open
Vdc
Vac
205
410
540
540
FI
DE
Txt VM DP
ND
1
0
FI
DE
Txt VM DP
ND
1
www.controltechniques.com
Electrical
Getting
Optimisation
installation
started
RA
NC
NV
PT
US RW BU
1
75
150
225
225
RA
NC
NV
PT
US RW BU
1
RA
NC
NV
PT
US RW BU
1
Technical
Component
Parameters
data
sizing
PS
PS
PS
Diagnostics
99

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents