Power Module Over Current Detected From The Module Input Currents; Internal Power Supply Fault; 24V Internal Power Supply Overload; Power Module Power Supply Fail - Emerson SP1201 Installation Manual

Unidrive sp regen series 200v 400v 575v 690v
Table of Contents

Advertisement

Safety
Product
Introduction
Information
information
Trip
OI.AC
Instantaneous input over current detected: peak input current greater than 225%
Check correct regen inductor fitted
Check for short circuit on regen component circuitry
3
Check DC connections: Regen to motoring drive for short circuit
Check line synchronisation status
Reduce the values in current loop gain parameters - Pr 4.13 and Pr 4.14 (closed loop vector and servo modes only)
OIAC.P

Power module over current detected from the module input currents

Check correct regen inductor fitted
Check for short circuit on regen component circuitry
104
Check DC connections: Regen to motoring drive for short circuit
Check line synchronisation status
Reduce the values in current loop gain parameters - Pr 4.13 and Pr 4.14 (closed loop vector and servo modes only)
OIdC.P
Power module over current detected from IGBT on state voltage monitoring
Vce IGBT protection activated.
109
Check motor and cable insulation.
O.Ld1
Digital output overload: total current drawn from 24V supply and digital outputs exceeds 200mA
26
Check total load on digital outputs (terminals 24,25,26)and +24V rail (terminal 22)
OV
DC bus voltage has exceeded the peak level or the maximum continuous level for 15 seconds
Check nominal AC supply level
Check for supply disturbances which could cause the DC bus to rise – voltage overshoot after supply recovery from a notch induced
by DC drives.
Drive voltage rating
2
200
400
575
690
OV.P
Power module over voltage has exceeded the peak level or the maximum continuous level for 15 seconds
Check nominal AC supply level
Check for supply disturbances which could cause the DC bus to rise – voltage overshoot after supply recovery from a notch induced
by DC drives.
Drive voltage rating
106
200
400
575
690
PAd
Keypad has been removed when the drive is receiving the speed reference from the keypad
Fit keypad and reset
34
Change speed reference selector to select speed reference from another source
PS

Internal power supply fault

Remove any Solutions Modules and reset
5
Check integrity of interface ribbon cables and connections (size 4,5,6 only)
Hardware fault - return drive to supplier
PS.10V
10V user power supply current greater than 10mA
Check wiring to terminal 4
8
Reduce load on terminal 4
PS.24V

24V internal power supply overload

The total user load of the drive and Solutions Modules has exceeded the internal 24V power supply limit.
The user load consists of the drive's digital outputs plus the SM-I/O Plus digital outputs, or the drive's main encoder supply plus the
SM-Universal Encoder Plus and SM-Encoder Plus encoder supply.
9
Reduce load and reset
Provide an external 24V >50W power supply
Remove any Solutions Modules and reset
PS.P

Power module power supply fail

Remove any Solutions Modules and reset
108
Check integrity of interface ribbon cables and connections (size 4,5,6 only)
Hardware fault - return drive to supplier
SCL
Drive RS485 serial comms loss to remote keypad
Refit the cable between the drive and keypad
Check cable for damage
30
Replace cable
Replace keypad
210
System
Mechanical
Electrical
design
installation
installation
Peak voltage [0V]
Maximum continuous voltage level
415
830
990
1190
Peak voltage [0V]
Maximum continuous voltage level
415
830
990
1190
www.controltechniques.com
Getting
Optimisation
Parameters
started
Diagnosis
410
815
970
1175
410
815
970
1175
Technical
Component
Diagnostics
data
sizing
Unidrive SP Regen Installation Guide
Issue Number: 2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents