Common Dc Bus Fusing - Emerson SP1201 Installation Manual

Unidrive sp regen series 200v 400v 575v 690v
Table of Contents

Advertisement

Safety
Product
Introduction
Information
information
Table 10-18 SPMC / U input current, fuse and cable ratings
Typical input
Model
current
A
SPMC1402
339
SPMC2402
2 x 308
SPMU1401
207
SPMU1402
339
SPMU2402
2 x 339
SPMC1601
192
SPMC2601
2 x 170
SPMU1601
192
SPMU2601
2 x 170
10.3.2

Common DC Bus Fusing

DC bus fusing is required in the following systems for both the regen and
motoring drives, and the SPMC if used as the external soft start circuit.
1. Single regen, multiple motoring drives
2. Multiple regen, multiple motoring drives
3. Unidrive SP regen brake resistor replacement
4. Regen systems using an SPMC
DC bus fuses as detailed following must be fitted in both the positive and
negative branches of DC Bus connections to each of the regen and
motoring drives, and the SPMC if used as the external soft start circuit.
NOTE
Ferraz have a range of DC fuses which could be used to provide the
required protection, types (00 and 21) may be used.
00 - Fuse with no trip indicator fitted
21 - Fuse fitted with trip indicator
NOTE
The DC Bus voltage set-point on a regen system (default) is set to
700Vdc, this can be up to a maximum 800Vdc. Therefore ensure the
selected DC Bus fusing is of the correct voltage rating with regards to
the DC Bus voltage level (Pr 3.05 DC Bus Voltage Set-point).
Unidrive SP Regen Installation Guide
Issue Number: 2
System
Mechanical
design
installation
Maximum
Typical DC
input current
current
A
Adc
class gG UL
344
379
2 x 312
2 x 345
210
222
344
379
609
2 x 379
195
209
2 x 173
2 x 185
195
209
2 x 173
2 x 185
www.controltechniques.com
Electrical
Getting
Optimisation
installation
started
Semi-conductor fuse
in series with HRC fuse
HRC IEC
Semi-
conductor
class J
IEC class aR
540
400
2 x 120
450
400
2 x 120
250
315
2 x 70
540
400
2 x 120
450
400
2 x 120
250
250
2 x 70
250
250
2 x 70
250
250
2 x 70
250
250
2 x 70
Technical
Component
Parameters
data
Cable sizes
AC input
DC output
2
2
AWG
AWG
mm
mm
2 x 4/0
2 x 120
2 x 4/0
2 x 4/0
2 x 120
2 x 4/0
2 x 2/0
2 x 70
2 x 2/0
2 x 4/0
2 x 120
2 x 4/0
2 x 4/0
2 x 120
2 x 4/0
2 x 2/0
2 x 120
2 x 4/0
2 x 2/0
2 x 120
2 x 4/0
2 x 2/0
2 x 120
2 x 4/0
2 x 2/0
2 x 120
2 x 4/0
Diagnostics
sizing