This parameter is the r.m.s. input current to the drive. The phase currents consist of an active component and a reactive component. The three phase
currents can be combined to form a resultant current vector as shown below:
y
Resultant
output current
Pr 4.02
Pr 4.01
Pr 4.17
x
The resultant current magnitude is displayed by this parameter. The active current is the torque producing current for a motor drive and the real
current for a Regen drive. The reactive current is the magnetising or flux producing current for a motor drive.
4.02
Active current
Drive mode
Regen
Bit
SP
Coding
Range
Regen
Update rate
4ms
The active current is the real current in a Regen drive.
Direction of active current
+
-
The active current is aligned with the y axis of the reference frame. The y axis of the reference frame is aligned with the Regen drive terminal voltage