Output Sharing Chokes (For Motoring Drives Only); Figure 3-10 Output Sharing Choke Identification; 400 / 600V Output Sharing Choke Ratings; 400 / 600V Centre Tapped Output Sharing Choke Ratings - Emerson SP1201 Installation Manual

Unidrive sp regen series 200v 400v 575v 690v
Table of Contents

Advertisement

Safety
Product
Introduction
Information
information
3.7

Output Sharing Chokes (for motoring drives only)

The following section covers the output sharing chokes which are currently available for Unidrive SP. These being used for the motoring drives in a
regen system only (between drive and motor).

Figure 3-10 Output sharing choke identification

OTL:
Output sharing choke
Voltage rating
4: 380V to 480V
6: 500V to 690V
0: Single
1: Dual
Current rating step
NOTE
For the 200V SPMx modules used in parallel configurations and where output sharing chokes are required the 400V OTL output sharing chokes
should be used.
The following tables detail the output chokes required for the various configurations of paralleled SPMA and SPMD power modules.
When connecting either SPMA or SPMD drives in parallel
they must be de-rated by 5%
CAUTION
NOTE
In order to achieve the best possible current sharing between paralleled Unidrive SPM modules, sharing chokes must be fitted.
Table 3-9 400 / 600V output sharing choke ratings
Current
Inductance
Model
µH
A
OTL401
221
40.1
OTL402
267
34
OTL403
313
28.5
OTL404
378
23.9
OTL601
135
103.9
OTL602
156
81.8
OTL603
181
70.1
OTL604
207
59.2
Table 3-10 400 / 600V centre tapped output sharing choke ratings
Current
Inductance
Model
µH
A
OTL411
389.5
42.8
OTL412
470.3
36.7
OTL413
551
31.1
OTL414
665
26.6
OTL611
237.5
110.4
OTL612
273.6
88.4
OTL613
319.2
76.7
OTL614
364.8
65.7
The OTLX1X centre tapped output sharing chokes can only
be used when two Unidrive SPM drives are paralleled
together. For all other combinations the OTLX0X output
sharing choke must be used.
CAUTION
22
System
Mechanical
Electrical
design
installation
installation
OTL
4
0
1
Width (W)
Depth (D)
Height (H)
mm
mm
mm
240
220
210
242
220
205
242
220
205
242
220
205
242
170
203
242
170
203
242
200
203
242
200
203
Width (W)
Depth (D)
Height (H)
mm
mm
mm
300
150
160
300
150
160
300
150
160
300
150
160
300
150
160
300
150
160
300
150
160
300
150
160
www.controltechniques.com
Getting
Optimisation
Parameters
started
Weight
Part No.
kg
20
4401-0197-00
20
4401-0198-00
25
4401-0199-00
25
4401-0200-00
20
4401-0201-00
20
4401-0202-00
20
4401-0203-00
20
4401-0204-00
Weight
Part No.
kg
8
4401-0188-00
8
4401-0189-00
8
4401-0192-00
9
4401-0186-00
8
4401-0193-00
8
4401-0194-00
8
4401-0195-00
8
4401-0196-00
Technical
Component
data
sizing
Unidrive SP Regen Installation Guide
Issue Number: 2
Diagnostics

Hide quick links:

Advertisement

Table of Contents
loading