Optional External Emc Filter Terminal Data - Emerson SP1201 Installation Manual

Unidrive sp regen series 200v 400v 575v 690v
Table of Contents

Advertisement

Safety
Product
Introduction
Information
information
Table 10-35 Optional external EMC Filter terminal data
CT part
Manufacturer
number
4200-6118
4200-6119
4200-6210
4200-6305
4200-6307
4200-6309
4200-6406
Schaffner
4200-6408
4200-6503
4200-6504
4200-6603
4200-6604
4200-6316
4200-6315
4200-6120
4200-6121
4200-6211
4200-6306
4200-6308
4200-6405
Epcos
4200-6407
4200-6501
4200-6502
4200-6601
4200-6602
4200-6314
4200-6313
10.5.1
Varistors
AC line voltage transients can typically be caused by the switching of
large items of plant, or by lightening strikes on another part of the supply
network. If these transients are not suppressed, they can cause damage
to the insulation of the Regen inductors, or to the Regen drive
electronics. Varistors should be fitted after the supply fuses and before
the EMC filter as shown in the following.
Table 10-36 Varistors
Varistor
voltage
Drive rating
rating V
550
200V
(200V to 240V±10%)
680
550
400V
(380V to 480V±10%)
680
680
575V
(500V to 575V±10%)
1000
385
690V
(690V±10%)
1000
202
System
Mechanical
Electrical
design
installation
installation
Power connections
Max cable size
2
4mm
12AWG
2
10mm
8AWG
2
16mm
6AWG
2
50mm
0AWG
2
25mm
4AWG
2
95mm
4/0AWG
2
50mm
0AWG
Busbar arrangement
2
4mm
12AWG
2
10mm
8AWG
2
16mm
6AWG
2
10mm
8AWG
2
50mm
0AWG
2
95mm
4/0AWG
Busbar arrangement
Energy
Quantity
rating
per
J
system
RMS
620
3
760
3
620
3
760
3
760
3
1200
3
550
6
1200
3
www.controltechniques.com
Getting
Optimisation
started
Max torque
0.8 N m (0.6 lb ft)
2.0 N m (1.5 lb ft)
2.2 N m (1.6 lb ft)
8 N m (5.9 lb ft)
2.3 N m (1.7 lb ft)
20 N m (14.7 lb ft)
8 N m (5.9 lb ft)
0.6 N m (0.4 lb ft)
1.35 N m (1.0 lb ft)
2.2 N m (1.6 lb ft)
1.35 N m (1.0 lb ft)
6.8 N m (5.0 lb ft)
20 N m (14.7 lb ft)
Configuration
CT part number
Line to line
2482-3291
Line to ground
2482-3211
Line to line
2482-3291
Line to ground
2482-3211
Line to line
2482-3211
Line to ground
2482-3218
2 in series line to line
2482-3262
Line to ground
2482-3218
Technical
Component
Parameters
data
sizing
Ground connections
Ground stud size
Max torque
M5
3.5 N m (2.6 lb ft)
M6
3.9 N m (2.9 lb ft)
M10
25 N m (18.4 lb ft)
M6
3.9 N m (2.9 lb ft)
M10
25 N m (18.4 lb ft)
M5
3.0 N m (2.2 lb ft)
M6
5.1 N m (3.8 lb ft)
M10
10 N m (7.4 lb ft)
Unidrive SP Regen Installation Guide
Issue Number: 2
Diagnostics

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents