T9 Analogue Output 1 Scaling; T9 Analogue Output 1 Mode; T10 Analogue Output 2 Source; T10 Analogue Output 2 Scaling - Emerson SP1201 Installation Manual

Unidrive sp regen series 200v 400v 575v 690v
Table of Contents

Advertisement

Safety
Product
Introduction
Information
information
7.20

T9 analogue output 1 scaling

Drive mode
Regen
Bit
SP
Coding
Range
Regen
Default
Regen
Update rate
Background
7.21

T9 analogue output 1 mode

Drive mode
Regen
Bit
SP
Coding
Range
Regen
Default
Regen
Update rate
Background read
The following modes are available for the analogue outputs.
Parameter value
Parameter string
0
1
2
3
In voltage mode the output range is -10V to 10V. If the scaling parameter is 1.000 then -10V and 10V are produced when the source parameter is at -
maximum and maximum respectively. Different scaling can be applied with Pr 7.23. If the result of the scaling produces an output of more than +/-
100% the output is clamped within the +/-10V range.
In current modes with a scaling parameter of 1.000 the minimum and maximum current are produced when the source parameter is at 0 and
maximum respectively. Therefore in 4 - 20mA mode the output is 4mA when the source parameter is zero. Different scaling can be applied with
Pr 7.23. If the result of the scaling produces an output of more than 100% the output is clamped at 20mA
If high speed update mode is selected and the source for the output is one of the parameters designated for high speed analogue output operation
(see start of this section) the output is updated at a higher rate with special scaling. If the parameter selected is not designated for this mode the
output is updated at the normal rate. If speed feedback or power is selected for high speed mode for both analogue output 1 and analogue output 2
the setting is ignored for analogue output 2. If the high speed mode is selected the output is always a voltage signal.
7.22

T10 analogue output 2 source

Drive mode
Regen
Bit
SP
Coding
Range
Regen
Default
Regen
Update rate
Background
7.23

T10 analogue output 2 scaling

Drive mode
Regen
Bit
SP
Coding
Range
Regen
Default
Regen
Update rate
Background
Unidrive SP Regen Installation Guide
Issue Number: 2
System
Mechanical
design
installation
FI
DE
Txt VM
DP
ND
3
0.000 to 4.000
1.000
FI
DE
Txt VM DP
ND
1
0 to 3
0
Mode
VOLt
Voltage mode
0-20
0 - 20mA
4-20
4 - 20mA
H.Spd
High speed up date mode
FI
DE
Txt VM DP
ND
2
Pr 0.00 to Pr 21.51
Pr 5.05
FI
DE
Txt
VM
DP
ND
3
0.000 to 4.000
1.000
www.controltechniques.com
Electrical
Getting
Optimisation
installation
started
RA
NC
NV
PT
US RW BU
1
RA
NC
NV
PT
US RW BU
1
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
Technical
Parameters
data
PS
1
1
PS
1
1
PS
1
1
PS
1
1
Component
Diagnostics
sizing
127