Safety
Product
Introduction
Information
information
14.14
PID lower limit
Drive mode
Regen
Bit
SP
Coding
Range
Regen
Default
Regen
Update rate
Background
If Pr 14.18 = 0, the upper limit (Pr 14.13) defines the maximum positive output for the PID controller and the lower limit (Pr 14.14) defines the
minimum positive or maximum negative output. If Pr 14.18 = 1, the upper limit defines the maximum positive or negative magnitude for the PID
controller output. When any of the limits are active the integrator is held.
14.15
PID scaling
Drive mode
Regen
Bit
SP
Coding
Range
Regen
Default
Regen
Update rate
4ms
14.16
PID destination
Drive mode
Regen
Bit
SP
Coding
Range
Regen
Default
Regen
Update rate
Background
The value written to the destination parameter is (PID controller output x scaling) + PID main reference.
14.17
PID hold integrator
Drive mode
Regen
Bit
SP
Coding
1
Default
Regen
Update rate
4ms
When this parameter is set to 0 the integrator operates normally. Setting this parameter to 1 will cause the integrator value to be held. Setting this
parameter does not prevent the integrator from being reset to zero if the PID controller is disabled.
14.18
PID symmetrical limit enable
Drive mode
Regen
Bit
SP
Coding
1
Default
Regen
Update rate
Background
See Pr 14.13 and Pr 14.14.
176
System
Mechanical
design
installation
FI
DE
Txt VM DP
ND
2
±100.00 %
-100.00
FI
DE
Txt VM DP
ND
3
0.000 to 4.000
1.000
FI
DE
Txt VM DP
ND
1
2
Pr 0.00 to Pr 21.51
Pr 0.00
FI
DE
Txt VM DP
ND
0
FI
DE
Txt VM DP
ND
0
www.controltechniques.com
Electrical
Getting
Optimisation
installation
started
RA NC NV
PT
US RW BU
1
RA NC NV
PT
US RW BU
1
RA NC NV
PT
US RW BU
1
1
RA NC NV
PT
US RW BU
1
RA NC NV
PT
US RW BU
1
Technical
Component
Parameters
data
PS
1
PS
1
1
PS
1
1
PS
1
PS
1
Unidrive SP Regen Installation Guide
Diagnostics
sizing
Issue Number: 2