Input Inductance; Regen Status; Regen Restart Mode - Emerson SP1201 Installation Manual

Unidrive sp regen series 200v 400v 575v 690v
Table of Contents

Advertisement

Safety
Product
Introduction
Information
information

Input inductance

3.02
Drive mode
Regen
Bit
SP
Coding
Range
Regen
Update rate
Background
At power-up this parameter is zero. Each time the Regen drive is enabled the supply inductance is measured and displayed by this parameter. The
value given is only approximate, but will give an indication as whether the input inductance is correct for the sinusoidal rectifier unit size. The
measured value should include the supply inductance as well as the Regen drive input inductance, however, the supply filter capacitance, masks the
effect of the supply inductance. Therefore the value measured is usually the Regen drive input inductor value.

Regen status

3.03
Drive mode
Regen
Bit
SP
Coding
Range
Regen
Update rate
4ms
If an L.Sync trip occurs Pr 3.03 indicates the reason. At power-up and on trip reset this parameter is set to zero. Once an L.Sync trip has occurred this
parameter shows when the trip occurred and the reason for the last L.Sync trip as indicated by the bits in the table below. The reasons for the trip are
either because the supply frequency is out of range or the PLL (phase lock loop) within the drive cannot synchronise to the supply waveforms.
Bit
0
Tripped during synchronisation
1
Tripped while running
2
Reason for trip was supply frequency <30.0Hz
3
Reason for trip was supply frequency >100.0Hz
4
Reason for trip was PLL could not be synchronised

Regen restart mode

3.04
Drive mode
Regen
Bit
SP
Coding
Range
Regen
Default
Regen
Update rate
Background
Pr 3.04 defines the action taken after enable and when a synchronisation failure occurs.
0, rESYnC: Continuously attempt to re-synchronise
1, del.triP: delayed trip
Attempt to synchronise for 30s. If unsuccessful after this time then give a LI.SYnC trip. After a failure during running attempt to re-synchronise for 30s
before tripping.
2, triP: immediate trip
Attempt to synchronise for 30s. If unsuccessful after this time then give a LI.SYnC trip. After a failure during running, trip immediately.
96
System
Mechanical
design
installation
FI
DE
Txt VM DP
ND
3
1
0.000 to 500.000mH
FI
DE
Txt VM DP
ND
1
0 to 15
Status
FI
DE
Txt VM DP
ND
1
0 to 2
1
www.controltechniques.com
Electrical
Getting
Optimisation
installation
started
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
Technical
Component
Parameters
data
PS
1
PS
1
PS
1
1
Unidrive SP Regen Installation Guide
Diagnostics
sizing
Issue Number: 2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents