4.3.9 Connection of Miscellaneous Hardware

Miscellaneous non-signaling hardware (e.g., recorders, current meters) may be connected to a Point-to-
Point network in accordance with the following list.
No non-signaling hardware (meters or measuring devices) may be connected to a
Multi-Drop network since the transmitters, in this mode, do not output an analog
process variable.
Miscellaneous hardware may be series or parallel connected to the network according to its function.
Miscellaneous hardware must be passive two-terminal devices.
Miscellaneous hardware may not generate any type of noise or signals, other than noise that is
inherent in resistive components.
Individual miscellaneous hardware must meet the following requirements:
Capacitance to ground..........................50 pF maximum
Resistance to ground ............................1 MΩ minimum
Impedance if series connected ................Less than 10Ω
Impedance if parallel connected ......Greater than 50kΩ
The maximum number of miscellaneous devices per network is 16. The combined electrical
characteristics may not exceed the following:
Maximum capacitance to ground........................800 pF
Minimum resistance to ground ..........................62.5kΩ
Maximum series impedance..................................160Ω
Minimum parallel impedance .............................3125Ω
4-20
IMPORTANT
UMSITRPDS3-1
November 2010