Model 353/354
Terminals
I
AIN1
O
See Note 4
See Note 2
1.
Minimum network resistance equals the sum of the barrier resistances and the current sense resistor. Minimum
value is 250 Ohms; maximum value is 1100 Ohms.
2.
Connect the HART Communicator as shown in Figure 2-2 for hazardous and non-hazardous locations. The
HART Communicator is a non-polar device.
3.
Supply and return barriers are shown. Interconnect all cable shields and ground only at the barriers.
4.
Procidia (Model 353R or i|pac) terminal assignments are:
34 – Analog Input 1 +
35 – Analog Input 1 Common
33 – 24 Vdc
18 – Station Common
5.
For access to transmitter field terminals, remove the enclosure cap.
6.
Maximum cable length is as calculated using the formula in section 4.3.6.
FIGURE 4-8 Model 353/354 to Transmitter Connections (Analog Mode)
November 2010
Non-Hazardous
Location
250
See Note 1
20
21
5
See Note 3
6
GND
Common Ground Bus
Hazardous
Location
See Note 6
Transmitter
Terminals
See Note 5
Installation
_
+
-
+
4-20 mA
4-13