Siemens 7MF4333 User Manual page 139

Sitrans p, series dsiii transmitters for pressure, differential pressure, flanged level, and absolute pressure
Hide thumbs Also See for 7MF4333:
Table of Contents

Advertisement

UMSITRPDS3-1
Check Impulse Piping
Check that high and low pressure pipe connections are not reversed.
Check for leaks or blockage.
Check for entrapped gas in liquid lines or for liquid in dry lines.
Check for sediment in transmitter's process connection blocks.
Check that blocking valves are fully open and that bypass valves are tightly closed.
Check that the density of the fluid in piping is unchanged.
Check Loop Power Supply/Wiring
Check loop power supply for blown fuse or tripped circuit breaker.
Check for 10.5 Vdc minimum across loop +/- terminals in transmitter terminal compartment.
Check power supply output voltage: 15 Vdc minimum; 45 Vdc maximum (30 Vdc in an intrinsically
safe circuit).
Check polarity of loop wiring at both power supply and transmitter.
Check for loose or broken loop wiring at power supply terminals, supply barriers (if used), junction
boxes, and transmitter terminal compartment.
Check for disconnected or broken current sense resistor and for short between shield and loop + wire.
Check for accumulation of moisture in transmitter terminal compartment.
Check loop cable for proper type and length.
Check for electrical interference between the loop cable and any adjacent cables in a cable tray or
conduit.
Check Transmitter Configuration
Check for proper operating mode: analog, address 0; digital, address 1-15.
Check for appropriate transfer function (linear or square root).
Check the switch point if the square root output current characteristic (i.e. transfer function) is
configured.
Check for a Transmitter Stuck in Fixed Current (Loop Override) Mode
Re-enter Fixed Current mode from HART Communicator Online menu and properly exit the mode.
Check for Variable Process Fluid Flow
Install mechanical dampers in process pressure piping.
Select a higher damping value (software filter time constant).
Check Primary Element
Check that primary element is correctly installed.
Check element for damage and leaks.
Note any changes in process fluid properties that can affect output.
November 2010
Calibration And Maintenance
7-7