Network Junctions; Safety Barriers - Siemens 7MF4333 User Manual

Sitrans p, series dsiii transmitters for pressure, differential pressure, flanged level, and absolute pressure
Hide thumbs Also See for 7MF4333:
Table of Contents

Advertisement

UMSITRPDS3-1
Example Calculation:
Assume a network consists of two field instruments (both C
Let R = 250Ω, C = 40 pF/ft, C
Then L = (65,000,000 / (250 x 40)) – ((10,000 + 10,000) / 40) = 6000 feet (1800 meters)

4.3.7 Network Junctions

A network junction is shown in Figure 4-6. It is a wiring junction installed at a convenient point in the
loop to facilitate wiring, testing, and troubleshooting. Typically the junction is a conventional terminal
block mounted on a panel with a protective cover, cabinet, or junction box to enclose and protect wiring
terminals.
Multiple junctions can be installed to provide field access terminals for the connection of a HART
Communicator. Note the following:
Network with barriers – Locate a junction anywhere along the network in the non-hazardous area.
Network without barriers – A junction may be located anywhere along the network between the
power supply and transmitter.
A junction should be a simple electrical series connection containing NO repeaters or other devices
(active or passive) that can degrade HART communications.

4.3.8 Safety Barriers

Installed safety barriers must comply with the following:
Locate intrinsic safety barriers between the system power supply (e.g., Primary Master, if used)
residing in the non-hazardous area and the transmitter(s) in the hazardous area.
Combined or separate supply and return barriers may be used.
For an intrinsically safe application, the DC voltage applied to the safe side of the barrier must be 0.6
Vdc less than the rated barrier working voltage.
An active supply barrier must be operated within its specified input working voltage.
Barrier shunt impedance to ground to the HART range of frequencies (500 Hz to 2500 Hz) shall not
be less than 5000Ω.
Barrier end-to-end resistance, stated by the manufacturer, is used in calculating the maximum
Network cable length and minimum and maximum network voltages.
The barrier shall be installed and wired in accordance with the manufacturers instructions.
November 2010
= (1 + 1) x 5000 = 10,000
f
= 1).
n
Installation
4-19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7mf40337mf42337mf44337mf45337mf46337mf4812

Table of Contents