Connecting

5.1

Preparing the connection

Safety instructions
Always keep in mind the following safety instructions:
Only connect or disconnect in de-energized state.
Voltage supply
The data for power supply are specified in chapter ""Technical data".
Note
Power the transmitter via an energy-limited circuit (power max. 100 W) acc. to
IEC 61010-1, e.g.
Keep in mind the following additional factors that influence the operating voltage:
Connection cable
The device is supplied with a fixed connected cable. If an extension is required, a
shielded two-wire cable is recommended.
Shielded cable generally necessary in HART multidrop mode.
SITRANS LR110, HART
Operating Instructions, 10/2023, A5E49829006
Carry out electrical connection by trained, qualified personnel authorised by the
plant operator
WARNING
Class 2 power supply unit (acc. to UL1310)
SELV power supply unit (safety extra-low voltage) with suitable internal or
external limitation of the output current
Lower output voltage of the power supply unit under nominal load (e.g. with a
transmitter current of 20.5 mA or 22 mA in case of fault signal)
Influence of additional transmitters in the circuit (see load values in chapter
""Technical data")