7.4.3.4 IPS Check (Only for Italy CEI0-21 Grid Code)

Context
The Italy CEI0-21 grid code requires IPS check for the SUN2000L. During the self-check
process, the SUN2000L consecutively checks the protection thresholds and time for 10-min
overvoltage, level 1 overvoltage, level 1 undervoltage, level 1 overfrequency, and level 1
underfrequency. The SUN2000L shuts down after the check starts, and it restarts after the
check is successful.
Procedure
Step 1 On the Operation console screen, choose Device maintenance > IPS check to access the
IPS check screen.
Issue 02 (2017-12-12)
Description
The power grid will charge
the battery if Feed Power
into Grid is enabled.
Feed Power into Grid is set
to Disable by default. If this
function is enabled, comply
with the grid charge
requirements stipulated in
local laws and regulations.