Huawei SUN2000L User Manual page 101

Single-phase grid-tied pv string inverter
Hide thumbs Also See for SUN2000L:
Table of Contents

Advertisement

SUN2000L-(2KTL-5KTL)
User Manual
Table 7-9 Description of protection parameters
Parameter
Ins R protection threshold
(MΩ)
Phase protection point (º )
Phase angle offset
protection
10-min OV protection
threshold (V)
10-min OV protection
duration (ms)
Level-1 OV protection
threshold (V)
Level-1 OV protection
duration (ms)
Level-2 OV protection
threshold (V)
Level-2 OV protection
duration (ms)
Issue 02 (2017-12-12)
Description
To ensure device safety, the
SUN2000L detects the
insulation resistance of the
input side to the ground
when it starts a self-check. If
the detected value is less
than the preset value, the
SUN2000L does not start.
The Japanese standard
requires that during passive
islanding detection,
protection should be
triggered if an abrupt
voltage phase change is
detected.
The SUN2000L model
described in this document
does not support this
function. This function is
supported only by the model
with "-JP".
Under a specific grid code,
the SUN2000L needs to be
protected when the phase
angle offset of the three
phases of the power grid
exceeds a certain value.
Specifies the 10-minute
overvoltage protection
threshold.
Specifies the 10-minute
overvoltage protection
duration.
Specifies the level-1
overvoltage protection
threshold.
Specifies the level-1
overvoltage protection
duration.
Specifies the level-2
overvoltage protection
threshold.
Specifies the level-2
overvoltage protection
duration.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7 Operations on the Local FusionHome App
Value Range
[0.02, 1.5]
[3, 15]
Enable
Disable
[1xVn, 1.5xVn]
[50, 7200000]
[1xVn, 1.5xVn]
[50, 7200000]
[1xVn, 1.5xVn]
[50, 7200000]
94