Parameter
Level-1 UV protection
threshold (V)
Level-1 UV protection
duration (ms)
Level-2 UV protection
threshold (V)
Level-2 UV protection
duration (ms)
Level-1 OF protection
threshold (Hz)
Level-1 OF protection
duration (ms)
Level-2 OF protection
threshold (Hz)
Level-2 OF protection
duration (ms)
Level-1 UF protection
threshold (Hz)
Level-1 UF protection
duration (ms)
Level-2 UF protection
threshold (Hz)
Level-2 UF protection
duration (ms)

7.4.5.3 Feature Parameters

To set feature parameters, choose Grid-connect config > Expert > Feature parameters
from the Operation console screen
Issue 02 (2017-12-12)
Description
Specifies the level-1
undervoltage protection
threshold.
Specifies the level-1
undervoltage protection
duration.
Specifies the level-2
undervoltage protection
threshold.
Specifies the level-2
undervoltage protection
duration.
Specifies the level-1
overfrequency protection
threshold.
Specifies the level-1
overfrequency protection
duration.
Specifies the level-2
overfrequency protection
threshold.
Specifies the level-2
overfrequency protection
duration.
Specifies the level-1
underfrequency protection
threshold.
Specifies the level-1
underfrequency protection
duration.
Specifies the level-2
underfrequency protection
threshold.
Specifies the level-2
underfrequency protection
duration.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7 Operations on the Local FusionHome App
Value Range
[0.15xVn, 1xVn]
[50, 7200000]
[0.15xVn, 1xVn]
[50, 7200000]
[1xFn, 1.15xFn]
[50, 7200000]
[1xFn, 1.15xFn]
[50, 7200000]
[0.85xFn, 1xFn]
[50, 7200000]
[0.85xFn, 1xFn]
[50, 7200000]