Parameter
Reactive power change
gradient (%/s)
Reactive power
compensation (PF)
Reactive power
compensation (Q/S)
Freq for triggering OF
derating (Hz)
Freq for exiting OF derating
(Hz)
Recovery grad of OF
derating (%/min)

7.4.5.5 Time setting

To set time, choose Grid-connect config > Expert > Time setting from the Operation
console screen.
Issue 02 (2017-12-12)
Description
Adjusts the change speed of
the SUN2000L reactive
power.
Adjusts the SUN2000L
output power factor.
Adjusts the SUN2000L
output reactive power.
For a specific grid code, the
SUN2000L output active
power needs to be derated
when the grid frequency
exceeds a specific value.
Specifies the frequency
threshold for exiting
overfrequency derating.
Specifies the power
recovery gradient for
overfrequency derating.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7 Operations on the Local FusionHome App
Value Range
[0.1, 1000]
(–1, –0.8]U[0.8, 1]
[–0.6, 0.6]
When the output
frequency is 50 Hz, the
value range is
45.00–55.00 Hz.
When the output
frequency is 60 Hz, the
value range is
55.00–65.00 Hz.
When the output
frequency is 50 Hz, the
value range is
45.00–55.00 Hz.
When the output
frequency is 60 Hz, the
value range is
55.00–65.00 Hz.
[5, 20]