Emergency Power Off (Epo); Epo Cabling; Epo Operation; Preventive And Scheduled Maintenance / Part Replacement - Toshiba 1600XPi Series Installation And Operation Manual

8-22kva battery cabinet
Hide thumbs Also See for 1600XPi Series:
Table of Contents

Advertisement

The DC breaker on the battery cabinet is provided with a shunt trip. This device is operated with an applied
voltage of 120 Vac (supplied from the UPS). When the EPO is pressed the UPS applies 120V to the
shunt trip, causing the breaker to switch to the OFF position.
7.0

Emergency Power Off (EPO)

7.1

EPO Cabling

The Battery Cabinet does not have an EPO. The EPO on the UPS connects to the battery cabinet through
the battery cabinet connection cable between CN14 and CN14A. No other battery cabinet connection is
needed.
7.2

EPO Operation

Pressing the EPO will cause the breaker on the battery cabinet and the UPS, to switch to the OFF position
simultaneously, disabling both the battery cabinet and the UPS.
The DC breaker on the battery cabinet is provided with a shunt trip. This device is operated with an applied
voltage of 120 Vac (supplied from the UPS). When the EPO is pressed the UPS applies 120V to the
shunt trip, causing the breaker to switch to the OFF position.
8.0

Preventive and Scheduled Maintenance / Part Replacement

8.1

Preventive Maintenance

Toshiba's 1600XPi Series of UPS battery cabinets have been designed to provide years of trouble-free
operation requiring a minimum of preventive maintenance.
The best preventive measure that the battery cabinet user can take is to keep the area around the unit,
particularly the air inlet vents, clean and free of moisture and dust accumulations. If the atmosphere of the
installation site is very dusty, use a vacuum cleaner to periodically remove dust accumulations from the air
inlet vents. Schedule authorized service centers to perform internal parts inspections annually.
CAUTION
WARNING
8.2

Parts Replacement

The following list shows intervals for periodic maintenance and replacement of certain UPS parts.
12
Before performing any maintenance, the technician should become
familiar with and follow the important safety instructions on pages 1–4.
Proper maintenance of the battery system of this unit by factory authorized
personnel is essential to the safety and reliability of your battery cabinet
system. Refer to service manual.
Batteries: VRLA batteries are maintenance free with respect to electrolyte only. The charging
voltage, temperature, performance and connection resistance must be checked periodically.
Necessary corrective actions must be made in order to assure safe reliable power is supplied by
the battery cabinet. Charging voltage, storage/operating temperature, charging cycles, and
connection resistance all affect battery life.
The recommended battery replacement interval is 3 to 5 years. All of the batteries must be
replaced at the same time.
Monthly Maintenance
A. Visual Checks:
1. Leakage
2. Corrosion on positive terminal
B. Check battery temperature at the negative terminal.
1600XPi Series Battery Cabinet Installation and Operation Manual 64024-006