9.5
Backup Time at Partial Loads
Below is the estimated backup time at various fractions of full load for each 1000 Series
model. This table assumes the batteries are fresh and begin with a .full initial charge
Load
1000 VA Backup (min) 150
1500 VA Backup (min)
2000 VA Backup (min) 150
2400 VA Backup (min) 200
3000 VA Backup (min)
6000 VA Backup (min)
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
56
38
80
37
21
68
38
76
53
80
40
25
45
36
29
Table 9.1 – Backup Time vs. Partial Load
34
30
23
19
15
19
18
15
13
26
19
14
11
42
33
28
22
19
15
12
9
22
18
15
13
12
10
7
11
8
6
9
7
6
18
15
11
8
6
5
11
9
7