Addendum For Differential Pressure Transmitters: Selectable Output Functions - ABB 6X1EH Operating Instructions Manual

600t en series hart pressure transmitters
Hide thumbs Also See for 6X1EH:
Table of Contents

Advertisement

ADDENDUM FOR DIFFERENTIAL PRESSURE TRANSMITTERS:
SELECTABLE OUTPUT FUNCTIONS
GENERAL DESCRIPTION
The 600T Series Differential Pressure Transmitter provides a selection of output functions, as follows:
Linear
Sq. Root (x)
Sq. Root (x
3
5
Sq. Root (x
Polynomial
Costant current
where |x| and output are in the range 0 to 1 (0% to 100%).
Figure 1 shows the Input/output relationships with the different Square Root Options applied.
These output functions can be activated using a Configuration Tool like the Hand Held Communicator, a HART Universal
Communicator or a Personal Computer, carrying the Smart Configuration Program, connected to the transmitter via a Bell 202
modem (see the relevant Operating Instructions). In the Analog version the Sq. Root (x) can be selected through the use of a
hardware link (see the ADDENDUM use of Hardware links on the secondary electronics).
The output of the transmitter is actually the analog signal 4 to 20 mA and the digital signal read in engineering units on the integral
display.
Flow %/100
for differential pressure or level measurements
for flow measurements using restriction type primary element, like orifice plate,
integral orifice, Venturi or Dall tube and similar.
)
for open channel flow measurements using rectangular or trapezoidal weir
)
for open channel flow measurements using V-notch (triangular) weir.
for input linearization using a 5th-order polynomial function
for input linearization using 2 polynomial functions of 2nd order
for loop or associated equipment test.
1
0.9
0.8
Sq.Root x
0.7
0.6
Sq.Root x^3
0.5
0.4
0.3
0.2
0.1
0
0
0.1
0.2
0.3
Differential Pressure %/100
Sq.Root x^5
0.4
0.5
0.6
0.7
0.8
Fig. 1
0.9
1