ABB 6X1EH Operating Instructions Manual page 43

600t en series hart pressure transmitters
Hide thumbs Also See for 6X1EH:
Table of Contents

Advertisement

Sensor trimming
If a sensor trimming operation is requested for mod. 621ES level transmitter, follow the relevant procedure of the Hand Held
Communicator and PC Software instructions.
If the result is not satisfactory after having carried out either the ZERO TRIMMING or the FULL TRIMMING, the operation must
be repeated with a special variation for these transmitters.
This special procedure dedicated to the model 621ES level transmitter, is as follows:
a) LOW TRIM (low value) for FULL TRIM operation, or ZERO TRIM, only.
A standard operation must be performed according to the procedure. If the result is not satisfactory the operation must be
repeated with a similar procedure but with a new value which has to be entered. This value must be calculated, as follows,
taking in consideration the error with reversed sign:
V
new
entered
- 1st Example: Trimming at 10 mbar (applied value)
If the displayed value (via HART) after the first operation, is 10.2 mbar, then the error is +0.2 (10.2 - 10).
The new value to be therefore entered is 9.8 mbar (10 - 0.2).
- 2nd Example: Trimming at true zero (0 mbar)
If the displayed value (via HART) after the first operation, is -0.5 mbar, the operation must be repeated entering + 0.5 mbar.
Note: The LOW TRIM and ZERO TRIM operations affect the span as they do not change the upper
range value previously set. So a high trimming operation according to point b, is highly recommended.
b) HIGH TRIM (high value) for FULL TRIM operation.
A standard operation must be performed according to the procedure. If the result is not satisfactory the operation must be
repeated with a procedure similar to that shown at point a above.
(new calculated value with error taken with reversed sign).
Output % Reranging
Sometimes, in case of tank level measurement, it becomes difficult to calculate the LRV or the URV of the transmitter, or to empty
the tank for zero adjustment. So, not only with flange-mounted, but also with differential pressure transmitters using remote seals,
the Output % Reranging operation helps the user during transmitter calibration.
When it is know the level of the tank, expressed in percentage, the liquid level, it is possible to input this percentage that
automatically the transmitter recalculates its LRV and URV according to the new percentage value.
This can be done using a HART configuration tool on a 600T EN Transmitter, in Analog + HART version.
Two options are available as Output % Reranging operation:
1)
OP Range Low
2)
OP Range High
As example:
. . . ADDENDUM FOR FLANGE-MOUNTED TRANSMITTERS
V
=
applied - (
where both LRV and URV are adjusted
where only URV is change in accordance with the new input percentage
+
V
V
displayed -
applied)*
Actual level measured by the transmitter:
Transmitter output
Calibration :
a) New input level measurement (Option 1) = 30%
New calibration : LRV
The transmitter output is now = 30%
Starting again from the initial settings:
Transmitter output
Calibration :
b) New input level measurement (Option 2) = 30%
New calibration : LRV
The transmitter output is now = 30%
(*) error
= 27%
LRV
= -125 mbar
URV = +340 mbar
= -139.5 mbar
URV = +325.5 mbar
= 27%
LRV = -125 mbar
URV = +340 mbar
= -125 mbar
URV = +291.5 mbar
- 43 -

Advertisement

Table of Contents
loading

This manual is also suitable for:

6x1ed6x1ee6x1eg6x1es622ed6x1ea

Table of Contents