Technical specifications
16.5 Mechanical and climatic ambient conditions
Reduction of vibrations
If your S7-1500 automation system/ET 200MP distributed I/O system is exposed to severe
shock or vibration, take appropriate measures to reduce the acceleration or the amplitude.
We recommend the installation of the S7-1500 automation system/ET 200MP distributed I/O
system on damping materials (for example, rubber-bonded metal mounting).
Climatic ambient conditions
The following table shows the permissible climatic ambient conditions for the S7-1500
automation system/ET 200MP distributed I/O system:
Table 16- 8
Climatic ambient conditions
Ambient conditions
Temperature:
horizontal mounting posi-
tion:
vertical mounting position:
Temperature variation
Relative humidity
Barometric pressure
Pollutant concentration
324
Permissible range
0 °C to 60 °C
0 °C to 40 °C
10 K/h
from 10 % to 95 %
from 1140 to 795 hPa
ISA-S71.04 severity level G1; G2; G3
Comments
To increase the service life of the display, the
display switches off when the permitted op-
erating temperature is exceeded.
Further information about the temperatures
at which the display switches off and back on
again is available in the technical specifica-
tions of the manuals of the CPUs.
-
Without condensation, corresponds to rela-
tive humidity (RH) class 2 in accordance with
IEC 61131 part 2
corresponds to an altitude of -1000 m to
2000 m
-