14.6 Reset to factory settings
14.6.2

Resetting interface module (PROFINET IO) to factory settings

Function
The interface module can be reset to its factory state using "Reset to factory settings".
Method of resetting an interface module to factory settings
● Via STEP 7 (online via PROFINET IO)
Procedure using STEP 7
To reset an interface module to factory settings via STEP 7, follow these steps:
Make sure that an online connection to the interface module exists.
1. Open the online and diagnostics view of the interface module.
2. In the "Functions" folder, select the "Reset to factory settings" group.
3. Click the "Reset" button.
4. Click "OK" in response to the confirmation prompts.
Result: The interface module then performs a "Reset to factory settings".
298
Automation system
System Manual, 12/2017, A5E03461182-AE