Application planning
4.2 System and load power supply
CPU with
firmware version V2.1.0
CPU 1517T-3 PN/DP
CPU 1517TF-3 PN/DP
CPU 1518-4 PN/DP
CPU 1518F-4 PN/DP
CPU 1518-4 PN/DP MFP
CPU 1518F-4 PN/DP MFP
Connection, structure and configuration of an S7-1500 with PS 60W 24/48/60VDC HF
● You must insert the system power supply PS 60W 24/48/60VDC HF in slot 0.
Figure 4-9
● If you are using the PS 60W 24/48/60VDC HF, the 24 V supply of the CPU is not taken
into account in the power budget calculation. We therefore recommend that you do not
connect the 24 V DC to the CPU.
You must set the "System power supply" parameter to the option "No connection to
supply voltage L+" during configuration of the CPU. STEP 7 checks the setting when
compiling the configuration.
Figure 4-10
102
Hardware func-
tion version
FS01 or higher
FS01 or higher
FS03 or higher
FS03 or higher
FS01 or higher
FS01 or higher
Slot PS 60W 24/48/60VDC HF
Connecting PS 60W 24/48/60VDC HF
Article number
6ES7517-3TP00-0AB0
6ES7517-3UP00-0AB0
6ES7518-4AP00-0AB0
6ES7518-4FP00-0AB0
6ES7518-4AX00-1AB00
6ES7518-4FX00-1AB00
System Manual, 12/2017, A5E03461182-AE
Max. retentive
memory
8 MB
8 MB
20 MB
20 MB
20 MB
20 MB
Automation system