1MRS755769
5.1.13.
Voltage Relay
Technical Reference Manual
Table 5.1.12.-1 Recorded data
REGISTER
Data description
EVENT1
Phase-to-phase voltage U
*
rated voltage, U
U
.
31
Residual voltage U
*
voltage U
Maximum voltage value of the phase-to-phase voltages during the last fault
*
conditions in the network, measured as a multiple of the rated voltage U
Minimum voltage value of the phase-to-phase voltages during the last fault
*
conditions in the network, measured as a multiple of the rated voltage U
Maximum voltage value of the negative phase-sequence voltage during the
*
last fault conditions in the network, measured as a multiple of the rated
voltage U
U
, dashes are shown on the LCD and "999" when read via serial
2s
communication.
Minimum voltage value of the positive phase-sequence voltage during the
*
last fault conditions in the network, measured as a multiple of the rated
voltage U
U
, dashes are shown on the LCD and "999" when read via serial
1s
communication.
Maximum voltage value of the residual voltage U
*
conditions in the network, measured as a percentage of the rated voltage U
Duration of the last start of stages U>, U>>/U
*
and of the external trip, shown as a percentage of the set operate time, or of
the calculated operate time at IDMT characteristic. A value other than zero
indicates that the corresponding stage has started whereas a value which is
100% of the set or calculated operate time indicates that the operate time of
the stage has elapsed, that is, the stage has tripped. If the operate time of a
stage has elapsed but the stage is blocked, the value is 99% of the set or
calculated operate time.
Time stamp for the event. The time when the collected data was stored. The
*
time stamp is displayed in two registers, one including the date expressed as
yy-mm-dd, and the other including the time expressed as HH.MM;SS.sss.
EVENT 2
Same as EVENT 1.
EVENT 3
Same as EVENT 1.
EVENT 4
Same as EVENT 1.
EVENT 5
Same as EVENT 1.
Number of
The number of times each protection stage U>, U>>/U
starts
U
>> has started, counting up to 999.
0
Number of
Number of trips:
trips
Overvoltage stages U>, U>> and U
*
Undervoltage stages U<, U<< and U
*
Residual overvoltage stages U
*
External trip
*
When the counters reach their maximum values (65535), they roll over.

Communication ports

The relay is provided with an optical communication port (infrared) on the front
panel. Rear communication is optional and requires a communication module,
which can be provided with either a plastic fibre-optic, combined fibre-optic (plastic
measured at a time of trip as a multiple of the
12
. The same applies to phase-to-phase voltages U
0
measured at a time of trip as a percentage of the rated
0
.
n
. If stage U>> is not based on negative phase-sequence voltage
n
. If stage U<< is not based on positive phase-sequence voltage
n
2
> and U
0
REU 610
during the last fault
0
>, U<, U<</U
<, U
2
1
<, U<, U<</U
2
>
<
1
>>
0
and
23
n
.
n
.
n
>, U
>>
0
0
<, U
>,
1
0
55