1MRS755769
Voltage Relay
Technical Reference Manual
Table 5.2.3.-5
Digital inputs
Operating range
Rated voltage:
REU610CVVHxxx
REU610CVVLxxx
REU610CVVxxLx
REU610CVVxxHx
Current drain
Power consumption/input
Table 5.2.3.-6
Signal output SO1 and optional SO4 and SO5
Rated voltage
Continuous carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time constant
L/R <40 ms, at 48/110/220 V DC
Minimum contact load
Table 5.2.3.-7
Signal output SO2 , optional SO3, and IRF output
Rated voltage
Continuous carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time constant
L/R <40 ms, at 48/110/220 V DC
Minimum contact load
Table 5.2.3.-8
Power outputs (PO1, PO2, PO3)
Rated voltage
Continuous carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time constant
L/R <40 ms, at 48/110/220 V DC (PO1 with both contacts
connected in series)
Minimum contact load
Trip-circuit supervision (TCS):
Control voltage range
*
Current drain through the supervision circuit
*
Minimum voltage over a contact
*
DI1...DI2
110/125/220/250 V DC
24/48/60/110/125/
220/250 V DC
REU 610
±20% of the rated voltage
DI3...DI5 (optional)
24/48/60/110/125/
220/250 V DC
110/125/220/250 V DC
2...18 mA
≤0.9 W
250 V AC/DC
5 A
15 A
30 A
1 A/0.25 A/0.15 A
(5 A/3 A/1 A for series connection
of SO4 and SO5)
100 mA at 24 V AC/DC
250 V AC/DC
5 A
10 A
15 A
1 A/0.25 A/0.15 A
100 mA at 24 V AC/DC
250 V AC/DC
5 A
15 A
30 A
5 A/3 A/1 A
100 mA at 24 V AC/DC
20...265 V AC/DC
~1.5 mA
20 V AC/DC (15...20 V)
117