ABB REU 610 Technical Reference Manual page 115

Voltage relay
Hide thumbs Also See for REU 610:
Table of Contents

Advertisement

1MRS755769
Voltage Relay
Technical Reference Manual
Table 5.2.2.-6
RS-485 rear connector (DNP 3.0)
Terminal
Function
X5.8-8
Data A (+ RX)
X5.8-7
Data B (- RX)
X5.8-6
Data A (+ TX)
X5.8-5
Data B (- TX)
X5.8-4
Signal GND (for potential balancing)
X5.8-3
-
X5.8-2
Shield GND (via capacitor)
X5.8-1
Shield GND
Table 5.2.2.-7
Jumper numbering
Terminal
Function
X8
Pull-up
X6
Termination
X7
Pull-down
X13
Pull-up
X12
Termination
X11
Pull-down
X14
4-wire/2-wire
Fig. 5.2.2.-3
Jumper location on the DNP 3.0 communication module
Signal
Data A (+ TX)
TX
Data B (- TX)
Data A (+ RX)
RX
Data B (- RX)
-
X13
ON
ON
X8
X12
ON
ON
X6
X11
ON
ON
X7
X14
4-Wire
2-Wire
REU 610
A040357_2
115

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents