Target Led For Front Communication; How To Select The Protocol For Rear Communication - ABB REM 610 Operator's Manual

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

REM 610
REM 610
Main Menu
MEASUREMENTS
RECORDED DATA
SETTINGS
CONFIGURATION
INFO
Fig. 4.1.10.-1
Switching between the front and rear connections
4.1.10.1.
4.1.11.
24
Motor Protection Relay
Operator's Manual - ANSI version
1. Press an arrow button to access the main menu.
2. Use the arrow buttons to select CONFIGURATION\COMMUNICATION and
. The cursor is at the setting currently in use (REAR CONNECTION or
press
FRONT CONNECTION).
3. Press
to enter the setting mode. The second line starts to flash.
4. Use
or
to select the wanted setting.
5. Press
to confirm the selection.
6. Press
to return the display to the idle mode.
When the front connection has been selected and there is no communication for
approximately five minutes, the rear connection is automatically activated. To keep
the front connection continuously active, press
connecting the auxiliary voltage to the relay.
When the rear connection is selected, the selected rear protocol is
automatically activated.
Group Menu
CONFIGURATION
FUNCTION TEST/DI
COMMUNICATION
LANGUAGE
MEMORY SETTINGS
FREQUENCY
HMI PASSWORDS
TIME
TRIP CIRCUIT SUP
RTD INPUTS
STORE COUNTER

Target LED for front communication

Target off: the rear communication is currently selected.
*
Lit target: the front communication port is currently selected.
*
Flashing target: the front communication port is currently selected and the relay
*
is communicating.

How to select the protocol for rear communication

REM 610 allows you to choose the communication protocol for rear connection.
Parameter Menu
CONFIGURATION
REAR CONNECTION
REAR PROTOCOL
REAR COM. MODULE
SPA SETTINGS
IEC103 SETTINGS
MODBUS SETTINGS
UNIT ADDRESS
:xxx
COUNTER
:xxx
LINE-IDLE STATE
CONNECTION TYPE
1MRS755538
and
simultaneously when
Confirm
Cancel
CONFIGURATION
REAR CONNECTION
FRONT CONNECTION
A040243_2

Advertisement

Table of Contents
loading

Table of Contents