ABB REU 610 Technical Reference Manual page 42

Voltage relay
Hide thumbs Also See for REU 610:
Table of Contents

Advertisement

REU 610
Table 5.1.4.7.-7
SGB1...SGB5
Switch
Function
SGB1...5/1
0 = indications are not cleared by the digital input signal
*
1 = indications are cleared by the digital input signal
*
SGB1...5/2
0 = indications are not cleared and latched output contacts are not unlatched by the digital
*
input signal
1 = indications are cleared and latched output contacts are unlatched by the digital input
*
signal
SGB1...5/3
0 = indications and memorized values are not cleared and latched output contacts are not
*
unlatched by the digital input signal
1 = indications and memorized values are cleared and latched output contacts are unlatched
*
by the digital input signal
SGB1...5/4
Switching between setting groups 1 and 2 by using the digital input
0 = the setting group cannot be changed using the digital input
*
1 = the setting group is changed by using the digital input. When the digital input is energized,
*
setting group 2 is activated, if not, setting group 1 is activated.
SGB1...5/5
Time synchronization by the digital input signal
SGB1...5/6
External tripping by the digital input signal
SGB1...5/7
External triggering of the CBFP by the digital input signal
SGB1...5/8
External triggering of the trip lockout by the digital input signal
SGB1...5/9
Resetting of the trip lockout by the digital input signal
SGB1...5/10
Blocking of tripping of stage U> by the digital input signal
SGB1...5/11
Blocking of tripping of stage U>> or U
SGB1...5/12
Blocking of tripping of stage U< by the digital input signal
SGB1...5/13
Blocking of tripping of stage U<< or U
SGB1...5/14
Blocking of tripping of stage U
SGB1...5/15
Blocking of tripping of stage U
ΣSGB1...5
42
Voltage Relay
Technical Reference Manual
When SGB1...5/4 is set to 1, it is important that the switch has the same setting
in both setting groups.
> by the digital input signal
2
<; by the digital input signal
1
> by the digital input signal
0
>> by the digital input signal
0
SGR1...SGR8
The start, trip and alarm signals from the protection stages and the external trip
signal are routed to the output contacts with the switches of switchgroups SGR1...
SGR8.
The signals are routed to PO1...PO3 with the switches of switchgroup SGR1...SGR3
and to SO1...SO5 with those of SGR4...SGR8.
The matrix below can be of help when making the wanted selections. The start, trip
and alarm signals from the protection stages and the external trip signal are
combined with the output contacts by encircling the wanted intersection point. Each
intersection point is marked with a switch number, and the corresponding weighting
factor of the switch is shown to the right in the matrix. The switchgroup checksum is
obtained by vertically adding the weighting factors of all the selected switches of the
switchgroup.
1MRS755769
Default setting
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0