ABB REU 610 Technical Reference Manual page 71

Voltage relay
Hide thumbs Also See for REU 610:
Table of Contents

Advertisement

1MRS755769
Table 5.1.15.1.-14Fault record
Address
Signal name
601
Latest selection code
602
Sequence number
603
Unread records left
604
Time stamp of the recorded data, date
605
Time stamp of the recorded data, date and time
606
Time stamp of the recorded data, time
607
Time stamp of the recorded data, time
608
Phase-to-phase voltage U
609
Phase-to-phase voltage U
610
Phase-to-phase voltage U
611
Residual voltage U
612
Maximum pick-up phase-to-phase voltage
613
Minimum pick-up phase-to-phase voltage
614
Maximum pick-up negative phase-sequence voltage U
615
Minimum pick-up positive phase-sequence voltage U
616
Maximum residual voltage U
617
Start duration of stage U>
618
Start duration of stage U>>
619
Start duration of stage U<
620
Start duration of stage U<<
Voltage Relay
Technical Reference Manual
15
401
Reserved
402
403
FR ER
Fig. 5.1.15.1.-2
Status registers
When the value of the FR/ ER bit is 1, there is one or several unread fault/event
records. If time synchronization is realized via a digital input, either the SP (second-
pulse) or MP (minute-pulse) bit will be activated.
Refer to Table 5.1.18.-1 for IRF codes and Table 5.1.18.-2 for warning codes.
Structure 2
This structure contains data recorded during a fault sequence. Refer to Fault records
earlier in this section for the reading method.
a)
12
23
31
0
0
8
7
IRF code
Warning code
Reserved
Range
1...2
1...255
0...6
0...999
0...200
0...200
0...200
0...200
0...200
0...200
0...200
2s
0...200
1s
0...200
0...100
0...100
0...100
0...100
REU 610
0
SP MP
A040333
Comment
1 = read oldest unread record
2 = read oldest stored record
2 bytes: YY.MM
2 bytes: DD.HH
2 bytes: MM.SS
0...999 ms
0...2 × U
n
0...2 × U
n
0...2 × U
n
0...200% U
n
0...2 × U
n
0...2 × U
n
b)
0...2 × U
n
b)
0...2 × U
n
0...200% U
n
0...100%
0...100%
0...100%
0...100%
71