Ethernet; Station Communication - ABB REC650 Product Manual

Relion 650 series
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

Bay control REC650 2.2
Product version: 2.2
synchronization method that can be used to maintain a
common time within a station. This time can be synchronized
to the global time using, for instance, a GPS receiver. If PTP
is enabled on the IEDs and the switches that connect the
station are compatible with IEEE 1588, the station will
become synchronized to one common time with an accuracy
of under 1us. Using an IED as a boundary clock between
several networks will keep 1us accuracy on three levels or
when using an HSR, 15 IEDs can be connected in a ring
without losing a single microsecond in accuracy.

11. Ethernet

Access points
An access point is an Ethernet communication interface for
single or redundant station communication. Each access
point is allocated with one physical Ethernet port, two
physical Ethernet ports are allocated if redundant
communication is activated for the access point.
Device 1
AP1
AP2
AP3
SFP_301
SFP_302
SFP_303
IEC16000092 V1 EN-US
Figure 5.
Access points, non redundant (left) and redundant
communication (right)
Access points diagnostics
The access point diagnostics function blocks (RCHLCCH,
SCHLCCH and FRONTSTATUS) supervise communication.
SCHLCCH is used for communication over the rear Ethernet
ports, RCHLCCH is used for redundant communications over
the rear Ethernet ports and FRONTSTATUS is used for
communication over the front port. All access point function
blocks include output signal for denial of service.
Redundant communication
IEC 62439-3 redundant communication PRP
Redundant communication according to IEC 62439-3 PRP-0,
IEC 62439-3 PRP-1 parallel redundancy protocol (PRP) is
available as an option when ordering IEDs. PRP according to
IEC 62439-3 uses two optical Ethernet ports.
IEC 62439-3 High-availability seamless redundancy HSR
Redundant station bus communication according to IEC
62439-3 Edition 2 High-availability seamless redundancy
(HSR) is available as an option when ordering IEDs.
Redundant station bus communication according to IEC
62439-3 uses two optical Ethernet ports.
The HSR ring supports the connection of up to 30 relays. If
more than 30 relays are to be connected, it is recommended
to split the network into several rings to guarantee the
performance for real-time applications.
24
GUID-6E5D2696-A8EE-43E7-A94B-69C3D0612127 v2
Device 1
AP1
AP2
SFP_301
SFP_302
IEC16000092-1-en.vsdx
GUID-20F64A6D-AA8C-47D7-AA7D-4810996B2FF2 v2
GUID-A90FDBA7-D4D7-4CBD-9F05-13DCC9971779 v7
Routes
A route is a specified path for data to travel between the
source device in a subnetwork to the destination device in a
different subnetwork. A route consists of a destination
address and the address of the gateway to be used when
sending data to the destination device, see Figure 6.
Source
IEC16000095 V1 EN-US
Figure 6.
Route from source to destination through gateway

12. Station communication

AP3
SFP_303
Communication protocols
Each IED is provided with several communication interfaces
enabling it to connect to one or many substation level
systems or equipment, either on the Substation Automation
(SA) bus or Substation Monitoring (SM) bus.
Available communication protocols are:
• IEC 61850-8-1 communication protocol
• IEC/UCA 61850-9-2LE communication protocol
• LON communication protocol
• SPA communication protocol
• IEC 60870-5-103 communication protocol
Several protocols can be combined in the same IED.
IEC 61850-8-1 communication protocol
IEC 61850 Ed.1 or Ed.2 can be chosen by a setting in
PCM600. The IED is equipped with four optical Ethernet rear
ports for IEC 61850-8-1 station bus communication.The IEC
61850-8-1 communication is also possible from the electrical
Ethernet front port. IEC 61850-8-1 protocol allows intelligent
electrical devices (IEDs) from different vendors to exchange
information and simplifies system engineering. IED-to-IED
communication using GOOSE and client-server
communication over MMS are supported. Disturbance
recording file (COMTRADE) uploading can be done over MMS
or FTP.
The front port is only intended for PCM600
communication, maintenance, training and
1MRK 511 426-BEN B
GUID-95F9C7BA-92F8-489F-AD0A-047410B5E66F v1
Default gateway
Gateway
Destination
IEC16000095-1-en.vsdx
M14815-3 v14
M14787-3 v16
ABB