1MRS755769
5.1.17.1.
Voltage Relay
Technical Reference Manual

Event codes

Special codes are determined to represent certain events, such as start and tripping
of protection stages and different states of output signals.
The events are stored in the event buffer of the relay. The maximum capacity of the
buffer is 100 events. Under normal conditions the buffer is empty.
The contents of the buffer can be read using the L command, 5 events at a time.
Using the L command erases the previously read events from the buffer, with the
exception of events E50 and E51 which have to be reset by using the C command. If
a fault occurs and reading fails for example in data communication, the events can
be re-read by using the B command. If needed, the B command can also be repeated.
The L and B commands are only available on channel 0.
Events to be included in the event reporting are marked with the multiplier 1. The
event mask is formed by the sum of the weighting factors of all those events which
are to be included in event reporting.
Table 5.1.17.1.-1 Event masks
Event mask
Code
V155
E31...E36
1V155
1E1... 1E16
1V156
1E17...1E24
1V157
1E25...1E30
2V155
2E1...2E16
2V156
2E17...2E26
Channel 0
Events always included in the event reporting:
Table 5.1.17.1.-2 Event codes E1... E4
Channel
Event
Description
0
E1
IRF
0
E2
IRF disappeared
0
E3
Warning
0
E4
Warning disappeared
Table 5.1.17.1.-3 Event codes E50...E51
Channel
Event
Description
0
E50
Relay restart
0
E51
Event buffer overflow
Events possible to mask out:
Setting range
Default setting
0...63
1
0... 65535
21845
0... 255
85
0... 63
1
0...65535
3
0...1023
0