ABB REU 610 Technical Reference Manual page 41

Voltage relay
Hide thumbs Also See for REU 610:
Table of Contents

Advertisement

1MRS755769
Table 5.1.4.7.-5 SGF4 (Continued)
Switch
Function
SGF4/7
Start and trip criteria for stage U<
0 = stage operates when one of the phase-to-phase voltages falls below the set start value.
*
1 = stage operates when all the phase-to-phase voltages fall below the set value.
*
SGF4/8
Start and trip criteria for stage U<<
0 = stage operates when one of the phase-to-phase voltages falls below the set start value.
*
1 = stage operates when all the phase-to-phase voltages fall below the set value.
*
SGF4/9
U< Alarm mode selection
0 = normal operation of stage U<, used for tripping purposes
*
1 = stage U< operates as U< Alarm.
*
The alarm signal is routed to stage U trip in relay matrix, and the start signal of stage U< is
inhibited. When the alarm signal is active, the start LED is lit.
SGF4/10
Internal blocking of start and trip of stage U
voltages falls below 0.15 × U
0 = internal blocking of start and trip of stage U
*
1 = no internal blocking of start and trip of stage U
*
ΣSGF4
a)
If the switch SGF4/1 is set to 1, the switches SGF4/5...8 are overridden. Thereby all the stages use only phase U
are not checked or used.
Table 5.1.4.7.-6
SGF5
Switch
Function
SGF5/1
Selection of the latching feature for programmable LED1
SGF5/2
Selection of the latching feature for programmable LED2
SGF5/3
Selection of the latching feature for programmable LED3
SGF5/4
Selection of the latching feature for programmable LED4
SGF5/5
Selection of the latching feature for programmable LED5
SGF5/6
Selection of the latching feature for programmable LED6
SGF5/7
Selection of the latching feature for programmable LED7
SGF5/8
Selection of the latching feature for programmable LED8
When the switch is in position 0 and the signal routed to the LED is reset, the programmable
*
LED is cleared.
When the switch is in position 1, the programmable LED remains lit although the signal
*
routed to the LED is reset.
A latched programmable LED can be cleared either via the HMI, a digital input or the serial bus.
ΣSGF5
Voltage Relay
Technical Reference Manual
a)
a)
This switch has no effect if stage U<< is based on positive-phase-sequence
calculation.
.
n
SGB1...SGB5
The DI1 signal is routed to the functions below with the switches of switchgroup
SGB1, the DI2 signal with those of SGB2, and so forth.
> when one of the measured phase-to-phase
2
>
2
>
2
REU 610
Default setting
0
1
0
0
128
as input, and other phases
12
Default setting
0
0
0
0
0
0
0
0
0
41